APPENDICES
Device
Signal name
number
M9073
PCPUWDT error flag
M9074
PCOU ready completion flag
M9075
Test mode flag
M9076
External rapid stop input flag
M9077
Manual pulse generator axis setting error flag
M9078
Test mode request error flag
M9079
Servo program setting error flag
POINTS
(1) All special relays, M, are turned OFF by turning the power, OFF,
performing latch clear, or resetting with the RESET key switch.
When the RUN key switch is set to "STOP", the special relay settings are
retained.
(2) The special relays marked "Note-1" in the table above remain "ON" even
after a return to normal. They must therefore be turned OFF by using one
of the following methods.
(a) Method using the user program
Insert the ladder block at right into the program and turn the reset
execution command contact ON to clear the special relay.
(b) Method using a peripheral device
Perform a forced reset using the test function of the peripheral
device.
For details on this operation, refer to the manual for the peripheral
device.
(c) Turn the special relay OFF by setting the RESET key switch on the
front panel of the CPU module to "RESET".
Reset execution
command
(3) The ON/OFF status of special relays marked "Note-2" in the table above
is controlled by the sequence program.
(4) The ON/OFF status of special really marks "Note-3"in the tables above is
controlled by the test mode for the peripheral device.
(5) The special relays marked "Note-4" are reset only when power is
switched from OFF to ON.
PCPU→SCPU
RST
M9000
Enter the special relay
to be reset here.
APP − 42