Installing An Ac Power Supply - Cisco Nexus 9364C-GX Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Replacing Components
a. Push the orange plastic button on the top of the connector block inward toward the power supply.
b. Pull the connector block out of the power supply.
Step 3
Grasp the power supply handle while pressing the release latch towards the power supply handle.
Step 4
Pull the power supply out of the bay.
What to do next
You are ready to install a DC power supply in the open slot.

Installing an AC Power Supply

You can replace one power supply while the other one provides power to the switch.
Before you begin
• The power supply that you are installing must be capable of using the same airflow direction as the fan
• An AC power source must be within reach of the power cable that will be used with the replacement
• There must be an earth ground connection to the chassis that you are installing the replacement module.
Step 1
Holding the replacement power supply with one hand underneath the module and the other hand holding the handle, turn
the power supply so that its release latch is on the side and align the back end of the power supply (the end with the
electrical connections) to the open power supply slot before carefully sliding the power supply all the way into the slot
until it clicks into place.
Note
If the power supply does not fit into the open slot, turn the module over before sliding it carefully into the open
slot.
Step 2
Test the installation by trying to pull the power supply out of the slot without using the release latch.
If the power supply does not move out of place, it is secured in the slot. If the power supply moves, carefully press it all
the way into the slot until it clicks in place.
Step 3
Attach the power cable to the electrical outlet on the front of the power supply.
trays installed in the same switch and it must use the same type of power source as the other power supply
installed in the same switch (do not mix AC and DC power supplies in the same switch).
Note
If the power supply that you are replacing has a different color handle than the
replacement power supply, verify that it has or will have the same airflow direction
as the other modules in the switch.
power supply. If you are using n+n power redundancy, there must be a separate power source for each
power supply installed in the chassis. Otherwise, only one power source is required.
Typically, the chassis is grounded by its metal-to-metal connection with a grounded rack. If you need to
ground the chassis, see
Grounding the Chassis, on page
18.
Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide
Installing an AC Power Supply
35

Advertisement

Table of Contents
loading

Table of Contents