Page 3
/or national electric codes. 4. Connect the conduit to the RSAP by punching the appropriately sized hole in a convenient location. 5. Referring to Figure 2.0, 3.0 and the corresponding UPS wiring diagram, connect the seven (7) pairs of twisted wire from the RSAP to the customer accessible alarm contact terminal bar in the UPS module.
Page 4
Operating Instructions ALARM SILENCE pushbutton is used to silence the alarm. MONITOR RESET pushbutton is used to reset the RSAP UPS FAULT alarm. The monitor will alarm again if the alarm condition is still present following the RESET. Monitor TEST pushbutton is used to check the operation of all LED’s and the audible alarm. All LED’s that are illuminated will go off and all lights that are off will illuminate.