Hardware reset switch
When this switch is pressed, the AS311 will be reset. Use this switch when you
have changed the switch settings.
Channel 1 and channel 2 serial ports
Used to connect the serial transmission line (RS-232C or RS-422). D-Sub 25-pin
female connectors are provided on the AS311.
The pin assignment is as follows.
Channel 1
(RS-232C/RS-422)
1
FG
2
TXD
3
RXD
4
RTS
5
CTS
6
7
SG
8
9
5 Vdc
10
TXDA
11
RXDA
12
RTSA
13
CTSA
14
15
16
17
18
19
20
DTR
21
TXDB
22
RXDB
23
RTSB
24
CTSB
25
The arrow on the above figure shows the signal direction.
FG is connected with the T3's frame ground internally. (both channels)
DTR and RTS are ON while power is on.
Data transmitting is available when CTS is ON. DSR has no effect for transmission.
Pin 9 (5 Vdc) can be used to supply 5 Vdc power. (total max. 50 mA)
for RS-232C
for RS-422
for RS232C
for RS-422
1. AS311 Overview
Channel 2
(RS-232C)
1
FG
2
TXD
3
RXD
4
RTS
5
CTS
6
DSR
7
SG
8
9
5 Vdc
10
11
12
13
14
15
16
17
18
19
20 DTR
21
22
23
24
25