Rack and Cabinet Requirements

Rack and Cabinet Requirements
You can install the following types of racks or cabinets for your switch:
• Standard perforated cabinets
• Solid-walled cabinets with a roof fan tray (bottom-to-top cooling)
• Standard open four-post Telco racks
• Standard open two-post Telco racks
Work with your cabinet vendors to determine which of their cabinets meet the following requirements or see
the Cisco Technical Assistance Center (TAC) for recommendations:
• Use a standard 19-inch (48.3-cm), four-post Electronic Industries Alliance (EIA) cabinet or rack with
• The depth of a four-post rack must be 24 to 32 inches (61.0 to 81.3 cm) between the front and rear
• Required clearances between the chassis and the edges of its rack or the interior of its cabinet are as
Also, you must have power receptacles that are located within reach of the power cords that are used with the
switch.
Warning
Statement 1048 Rack Stabilization
The rack stabilizing mechanism must be in place, or the rack must be bolted to the floor before installation
or servicing. Failure to stabilize the rack can cause bodily injury.

Clearance Requirements

Provide the chassis with adequate clearance between the chassis and any other rack, device, or structure so
that you can properly install the chassis. Provide the chassis with adequate clearance to route cables, provide
airflow, and maintain the switch. For the clearances required for an installation of this chassis in a four-post
rack, see the following figure.
Cisco Nexus 93120TX NX-OS Mode Switch Hardware Installation Guide
10
mounting rails that conform to English universal hole spacing per section 1 of the ANSI/EIA-310-D-1992
standard.
mounting rails (for proper mounting of the bottom-support brackets or other mounting hardware).
follows:
• 4.5 inches (11.4 cm) between the front of the chassis and the interior of the cabinet (required for
cabling).
• 3.0 inches (7.6 cm) between the rear of the chassis and the interior of the cabinet (required for airflow
in the cabinet if used).
• No clearance is required between the chassis and the sides of the rack or cabinet (no side airflow).