Possible Errors
Registration BAD
Timed Out
Registration BAD
Pri Sub ID BAD
Registration BAD
2nd Sub ID BAD
Registration BAD
Pri&Sec – IDs BAD
Registration BAD
Pri ID – Need PIN
Registration BAD
2nd ID – Need PIN
Registration BAD
Pri&2nd – Need PIN

Replacing an existing communicator

Enter PIN#
Registering ...
Registration
SUCCESS
Displayed if no response to the registration request is received.
Indicates the city, central station, or customer number for the labeled
account(s) is not accepted. The ID information was either entered in-
correctly, or the central station failed to pre-authorize programmed ID
numbers with AlarmNet customer service.
Indicates the city, central station, or customer number for the Second-
ary account is not accepted. The ID information was either entered
incorrectly, or the central station failed to pre-authorize programmed ID
numbers with AlarmNet customer service.
Displayed when both primary and secondary subscriber IDs are invalid.
Displayed if this is a repair/replacement, or an error was made in pro-
gramming the Primary account information of the communicator for an
existing account. This prompt appears for 2 seconds. See the Replac-
ing an existing communicator section below for further displays.
This prompt is displayed if this is a repair/replacement, or an error was
made in programming the Secondary account information of the com-
municator for an existing account. This prompt appears for 2 seconds.
See the Replacing an existing communicator section below for further
displays.
This prompt is displayed if this is a repair/replacement, or an error was
made in programming BOTH the Primary and Secondary account in-
formation of the communicator for an existing account. This prompt
appears for 2 seconds. See the Replacing an existing communicator
section below for further displays.
This prompt appears after pressing the [Shift] and down arrow [↓] on
the 7720P.
Note: If it is necessary to exit registration mode, press ESC from the
7720P programming tool.
Enter a 4-digit alphanumeric PIN number provided by your central sta-
tion, your dealer or an authorized AlarmNet representative.
Press the [Enter] key.
The registration message is sent and the unit waits for acknowledge-
ment.
If the PIN is valid, the new communicator is registered and the old unit
unregistered. Additionally, AlarmNet sends a substitution alarm to the
central station.