Low evaporation temperature EVD
AL28
compressor 4
High evaporation tempearture EVD
AL29
compressor 1 (MOP)
High evaporation tempearture EVD
AL30
compressor 2
High evaporation tempearture EVD
AL31
compressor 3
High evaporation tempearture EVD
AL32
compressor 4
Low suction temperatura EVD
AL33
compressor 1
Low suction temperatura EVD
AL34
compressor 2
Low suction temperatura EVD
AL35
compressor 3
Low suction temperatura EVD
AL36
compressor 4
AL37
Start failure compressor 1
AL38
Start failure compressor 2
AL39
Start failure compressor 3
AL40
Start failure compressor 4
AL41
Envelope alarm compressor 1
AL42
Envelope alarm compressor 2
AL43
Envelope alarm compressor 3
AL44
Envelope alarm compressor 4
AL45
Low pressure differential compressor 1
AL46
Low pressure differential compressor 2
AL47
Low pressure differential compressor 3
AL48
Low pressure differential compressor 4
High discharge gas temperature
AL49
compressor 1
High discharge gas temperature
AL50
compressor 2
High discharge gas temperature
AL51
compressor 3
High discharge gas temperature
AL52
compressor 4
AL53
Temperature sensor B1 error
Veco S
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto
0 sec
Warning
Auto5, M 10 sec
OFF compressor
Auto5, M 11 sec
OFF compressor
Auto5, M 12 sec
OFF compressor
Auto5, M 13 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
60 sec
OFF compressor
Manual
0 sec
OFF compressor
Manual
0 sec
OFF compressor
Manual
0 sec
OFF compressor
Manual
0 sec
OFF compressor
Auto
60 sec
OFF compressor
restart the system. If the error does not
go eway, contact the closest Climma
service center.
The evaporating temperature of the
system is too high, maybe the probe is
faulty. Try to reset manually the alarm,
then if it does not go away, shut off the
system, wait 1 minute, then try to
restart the system. If the error does not
go eway, contact the closest Climma
service center.
The suction temperature value is too
low, maybe there is not enough
refrigerant in the system and there's a
leak, or maybe a probe is faulty. Try to
reset manually the alarm, then if it does
not go away, shut off the system, wait 1
minute, then try to restart the system.
If the error does not go eway, contact
the closest Climma service center.
An error occured while starting
compressor. Check sea water flow in
case compressor's envelope reaches
zone 5 or zone 9. Then try to reset
manually the alarm, then if it does not
go away, shut off the system, wait 1
minute, then try to restart the system.
If the error does not go eway, contact
the closest Climma service center.
The compressor was working outside of
its "safe" zone, therefore the system
stopped. Check sea water flow in case
compressor's envelope reaches zone 5
or zone 9. Then try to reset manually
the alarm, then if it does not go away,
shut off the system, wait 1 minute, then
try to restart the system. If the error
does not go eway, contact the closest
Climma service center.
Delta Pressure < than minimum
required for lubrication --> The
difference between the suction and
discharge pressures is too low and it
can create problems to the compressor.
Try to reset manually the alarm, then if
it does not go away, shut off the
system, wait 1 minute, then try to
restart the system. If the error does not
go eway, contact the closest Climma
service center.
Discharge max. Temperature --> The
discharge temperature of the system is
too much and out of the allowed
values. Check that there is enough
water going through the condenser.
Try to reset manually the alarm, then if
it does not go away, shut off the
system, wait 1 minute, then try to
restart the system. If the error does not
go eway, contact the closest Climma
service center.
Temp. Probe B1 (set-point) faulty or
Installation Manual –Page 16 / 20