Technical Data - Honeywell 010690.01 Mounting And Connection Instructions

Mains/charger unit 12 v dc/32 ah
Table of Contents

Advertisement

Available languages

Available languages

6
Functional Description
(continued)
Collective faults:
The messages are transmitted via the outputs
- "Fault", HIGH active and
- "
Fault
", LOW active.
The following fault causes are possible:
Mains fault / accum. defective or missing /
Information on function of the fault outputs:
Version A:
With
resistor R33
Display of mains and accumulator fault
Version B:
Without
resistor R33
Disply of accumulator fault only.
Mains
, output, HIGH active.
This output is active during power on.
SE
(ST1/1), input, LOW active.
For connecting "
Fault
" outputs of additional emergency power
supplies (cascading).
5.

Technical Data

Rated operating voltage
Operating voltage range
Frequency
Power consumption
Maximum constant current
Short-term continuous current drain (5 min.) 2.5 A max.
Maximum charging current
Approved accum. capacity as per VdS
No. of connectable accumulators
Possible accu. combinations
Current consumption as per VdS
for 60 hours at 32 Ah accum. capacity
Permanent accumulator monitoring
Temperature-guided accum. charging voltage
Operating temperature range
Storage temperature range
Environmental class as per VdS
Dimensions - PCB:
Mounting and Connection Instruktions Mains/charger unit 12 V DC / 32 Ah
SE
input
230 V AC
-15 % to +10 %
40 Hz to 60 Hz
75 VA
2 A
(with
charged accum.)
1.1 A
32 Ah max.
2 max.
e.g. 2x10/ 2x16/ 1x26 Ah
approx. 500 mA
-5 °C to +45 °C
-25 °C to +70 °C
II
97.5 x 250 mm
6. Set charge terminating voltage
1. The power supply must have reached operating temper-
ature.
For this purpose it must be operated for at least two hours at
rated load and with closed housing.
2. Connect a
charged accumulator.
A not completely charged accumulator leads to a miss-
alignment.
3. Adjust the voltage at the accumulator terminals using the
potentiometer PO3 according to the ambient temperature at
the accumulator as per the following table.
Please take note of the type of accumulator.
ATTENTION:
Only alter the charge terminating voltage:
1. After measuring the exact temperature and
2. When the voltage deviates >200 mV from the set value as
per following table.
Sonnenschein accum.
A500 series
(Condition on delivery)
T (°C)
U (V)
L
0
14.50
+5
14.30
+10
14.10
+15
13.95
+20
13.80
+25
13.65
+30
13.50
+35
13.40
+40
13.30
+45
13.25
+50
13.20
All other types of
accumulators
T (°C)
U (V)
L
0
14.10
+5
13.95
+10
13.75
+15
13.60
+20
13.50
+25
13.45
+30
13.40
+35
13.35
+40
13.30
+45
13.25
+50
13.20