Outlines And Dimensions - Mitsubishi Electric PLFY-WP32VBM-E Technical & Service Manual

Ceiling cassettes
Hide thumbs Also See for PLFY-WP32VBM-E:
Table of Contents

Advertisement

5

OUTLINES AND DIMENSIONS

PLFY-WP32VBM-E.UK PLFY-WP40VBM-E.UK PLFY-WP50VBM-E.UK
<Standard Panel>
20~45
Fresh air
intake hole
160
Indoor unit/Outdoor unit
connecting terminal block
Power supply
Branch duct hole
terminal block
187.5
Suspension bolt
M10 or W3/8
Water pipe
60
From HBC unit:Rc3/4
Water pipe
To HBC unit:Rc3/4
Suspension bolt
lower edge
50~70
Control wire entry
M
Air intake grille
M
36
Corner pocket
Indoor unit
Ceiling
Grille
Obstacle
1500mm
or more
OCH586
Ceiling hole
860~910
20~45
810
Suspension bolt pitch
For MA-Remote controller
terminal block
24
160
840
Air purge valve
Drain pipe
connected to VP-25
284
377
Power supply wire,
Ceiling
Indoor unit/Outdoor unit
Grille
connecting wire entry
597
Air intake hole
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
M
Auto vane
(Air outlet)
M
Vane motor
500
83
Air outlet hole
36
950
Indoor unit
3000mm or more
1800mm or more
from floor
For high
attachment
Floor
Detail connecting of Branch duct(Both aspects)
20~45
(7.5)
Branch duct hole
Burring hole pitch
(7.5)
20~45
(
(
Connected the attached
flexible pipe or socket.
Keep approximatety
10 to 15mm space
between unit ceilling
and ceilling slab.
35
In case of standard grille: PLP-6BA/PLP-6BAMD
17
In case of Auto-Grille: PLP-6BAJ
In case of wireless remote
controller: PLP-6BALM
Emergency operation switch<Cooling>
and Emergency Up/Down switch<Up>
Emergency operation
switch<Heating>and
Emergency Up/Down switch<Down>
DEFROST/STAND BY lamp
Receiver
Operation lamp
Note 1. Please choose the Grille from a standard grille, Auto-Grille.
2. As for drain pipe, please use VP-25 (O.D. [32 PVC TUBE).
Drain pump inclusion.
Raise is max 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8.
(Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for
control/power wires connection.
5. The height of the indoor unit is able to be adjusted
with the grille attached.
6. For the installation of the optional high efficiency filter
or optional multi-functional casement. (Reference of the 2nd sheet of detailed Figure)
1) Requires 400 mm or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions * marked on the figure.
3) The optional high efficiency filter becomes optional
multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/Wear dew.)
8. As for necessary installation/service space, please refer to the under at figure.
13
13
90
100
100
90
Cut out hole
[175
14-[2.8
350
Burring hole
[150
Cut out hole
Detail drawing of fresh air intake hole
Burring hole
3-[2.8
Burring hole pitch
[125
Cut out hole
[100
Ceiling
Auto-Grille
Air intake grille Up/down distance
L.L Filter
Air intake grille
Unit: mm
100 130
Ceiling