Maintenance - Mitsubishi Electric SUHZ-SW VA Series Installation Manual

Air to water heat pump
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
6. Electrical work
6.2. Field electrical wiring
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity Main switch (Breaker)
Outdoor unit power supply
Outdoor unit power supply earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Outdoor unit L-N
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
*1. A breaker with at least 3 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.
*2. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
Warning:
There is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication
signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator
should be used between indoor unit and outdoor unit, please use 3-poles type.
Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fire or communication failure.

7. Maintenance

B
A
G
L
K
H
I
J
Indoor unit
Refrigerant gas cylinder for R410A with siphon
A
H
Union
Refrigerant (liquid)
B
I
Liquid pipe
Electronic scale for refrigerant charging
C
J
Gas pipe
Charge hose (for R410A)
D
K
Stop valve
Gauge manifold valve (for R410A)
E
L
Outdoor unit
Service port
F
M
Refrigerant gas cylinder
G
operating valve
Fig. 7-1
SUHZ-SW45
~/N (single), 50 Hz, 230 V
*1
3 × 1.5 (Polar)
*2
*2
*2
DC 12 V ~ DC 24 V
230 V
Single phase
Isolator
S1
Outdoor Unit
S2
S3
E
C
F
D
M
20 A
2 × Min. 2.5
1 × Min. 2.5
1 × Min. 1.5
AC 230 V
AC 230 V
3 poles isolator
7.1. Gas charge (Fig. 7-1)
1. Connect gas cylinder to the service port of stop valve (3-way).
2. Execute air purge of the pipe (or hose) coming from refrigerant gas cylinder.
3. Replenish specified amount of refrigerant, while running the outdoor unit
for cooling.
Note:
In case of adding refrigerant, comply with the quantity specified for the refrig-
erating cycle.
Caution:
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installa-
tion, reinstallation, or repairs to the refrigerant circuit.
• For additional charging, charge the refrigerant from liquid phase of the gas
cylinder.
If the refrigerant is charged from the gas phase, composition change may
occur in the refrigerant inside the cylinder and the outdoor unit. In this case,
ability of the refrigerating cycle decreases or normal operation can be im-
possible. However, charging the liquid refrigerant all at once may cause the
compressor to be locked. Thus, charge the refrigerant slowly.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm
water (under 40°C) during cold season. But never use naked fire or steam.
S1
Indoor Unit
S2
S3
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Suhz-sw45Suhz-sw45va

Table of Contents