Connectable components
9.2 PP 72/48D PN
LED displays
Each PROFINET port has two integrated LEDs displaying the link status (green) and activity
(yellow); see the chapter titled Application (Page 55).
The PP 72/48 D PN has the following additional LEDs, which provide information on the
module status:
Table 9- 11
LEDs: Status display
Name
Designation
H1
PowerOK
H2
PNSync
H3
PNFault
H4
DIAG1
H5
DIAG2
H6
OVTemp
Note
When the system is booting, LEDs H1, H2 and H3 are lit.
9.2.2

Mounting

The I/O module can be fastened to the wall of the control cabinet using a mounting plate and
M6 screws. The module must be installed according to EN 60204.
A protective conductor must be connected using the grounding screw.
Note
The type plate is fitted to the rear side of the mounting plate. It is advisable to make a note of
relevant data as it is no longer visible after installation.
96
Color
Description
Green
Lit: Power supply ok
Not lit: As soon as one of the generated logic voltages falls below its setpoint, a reset is
triggered and the PowerOK LED goes out.
Green
Lit: Task system is synchronized to the bus cycle clock.
Not lit: Task system is not synchronized to the bus cycle clock.
Flashes 0.5 Hz: Task system has synchronized to the bus cycle clock and cyclic data
exchange is running.
Red
Not lit: Module is operating without error.
Lit: A system error has occurred (faulty module, incorrect parameterization by the
PROFINET controller, etc. ).
Green
Reserved
Green
Reserved
Red
Overtemperature display
WARNING
NCU 7x0.3 PN
Manual, 09/2011, 6FC5397-1EP40-0BA0