Configuration / project engineering

9.2 Functions

9.2
Functions
Table 9-1
Factory setting
OFF
Without cross-circuit detection
NC contact/NO contact evaluation
Debounce time for sensor inputs ∼ 50 ms
Autostart cascading input
Automatic startup after power failure (not
permissible in conjunction with startup testing)
Automatic start after power failure
In the case of automatic startup after a power failure, the system starts without actuation of
the start button.
If the system is powered down (e.g. for maintenance work), make sure that a hazardous
state cannot arise as a result of an automatic startup when the power supply is activated
again.
28
Schematic
2 x 1-channel
Autostart sensor input
With startup testing
DANGER
DIP switch
ON
No.
1
With cross-circuit detection
2
NC contact/NC contact evaluation
3
1 x 2-channel
4
Debounce time for sensor inputs ∼ 10 ms
5
Monitored start sensor input
6
Monitored start cascading input
7
Without startup testing
8
Without automatic startup after power failure
Manual, 08/2007, GWA NEB 926 1579-02 DS 02
3TK2826 safety relay