Operation

8.6 LEDs, keys and their meanings (undelayed and delayed)

Table 8-6
Connecting terminals 3TK2826-*CW3.1/2/4 - undelayed and delayed enabling circuits
Connecting
Meaning
terminal
A1
24...240 V AC/DC
A2
Chassis ground/N
13, 14; 23, 24
Relay enabling circuit, normally-open, undelayed
31, 32
Relay signaling circuit, normally-closed (enabling circuit status), undelayed
47, 48; 57,58
Relay enabling circuit, normally-open, delayed
61,62
Relay signaling circuit, normally-closed (enabling circuit status), delayed
73, 74
Relay signaling circuit, normally-open (feedback circuit fault)
T1, T2
Test outputs with pulsed test signals
T3
Test output with static test signal (+24 V DC)
1
Cascading input/normal switching duty
Y12, Y22
Sensor inputs, channel 1, channel 2
Y33
Start button (start after upwards and downwards edge)
Y34
Feedback circuit (checked only for "closed" to enable operation without feedback)
8.6
LEDs, keys and their meanings (undelayed and delayed)
Table 8-7
LEDs - undelayed and delayed enabling circuits
LED
Status
Device
Off
Green
Flashing green
Yellow
Flashing yellow
Green/yellow
flashing
Red
OUT
Off
Green
Flashing green
IN
Off
Green
Flashing green
SF
Off
Red
Flashing red
24
Meaning
No / too low supply voltage or internal fuse tripped.
Supply voltage in the permissible operating range
Self-test during restart
Configuration mode DIP switch
Configuration error or
configuration mode for delay time
Delay time changed
Device defective -> Replace device
Device faulty (e.g. due to electromagnetic interference)→ Press Reset
Output passive
Output active
OFF-delayed output, time running
"closed"
RF not
if start condition met (the SF LED also flashes)
Input passive (or switch-on condition not satisfied)
Input active
Cross-circuit at the input, simultaneity of sensors not satisfied, wire breakage during safety
shutdown mat operation
No group fault
Group fault (wiring fault, cross-circuit, wire breakage in the case of safety shutdown
operation, configuration error) -> Eliminate the fault and press RESET
Group fault (RF fault, simultaneity condition of the sensors not satisfied)
3TK2826 safety relay
Manual, 08/2007, GWA NEB 926 1579-02 DS 02