Integrating UCS Components in the Dynamic Rack
• Cisco preconfigured racks have not been certified for air transport.
• The preracked Cisco UCS system must ship in an upright position.
• Angle brackets should be installed in the corners of the rack to ensure that the equipment is secure and
does not move during transport. See the following illustration to see the locations of the brackets and the
screws required to install them. These brackets should be removed when the rack reaches its final
destination.
Figure 41: Installing and Removing Rear Corner Angle Brackets
1
• UCS components may be damaged if the rack tips over during shipment. To avoid such damage, secure
the racks by strapping them down in the truck. Strapping the rack will help prevent it from tipping over
during transport to the customer site.
• On a Cisco R-Series rack, check to ensure that the rack mounting brackets are properly secured to the
pallet. The bracket with keyhole cutouts should be at an angle to the pallet deck and should not be loose.
The front hold-downs for Cisco R-Series rack are right-angled and sit flush to the pallet and frame. Ensure
that the bolt that secures the bracket to the frame is torqued to 70-100 in-lb. (6-9 N-m).
• Prepare the rack for shipment by attaching the packaging shown in the following illustration.
Cisco R42612 Rack and RP-Series Metered Input PDU Installation Guide
84
Bracket installed in the corner of the rack.
Integrating UCS Components in the Dynamic Rack
2
Screws that hold the bracket in place.