EK280
Message
Description, process
Vb Warn Lim.
The monitored volume at base conditions consumption value (standard: hourly
consumption) is outside the set warning limit values.
The monitored values and the warning limits can be adjusted using the configuration
program "enSuite".
Qm Warn Lim.
The actual flow rate (gas flow rate) is outside the set warning limit values.
The warning limits can be adjusted using the configuration program "enSuite".
T Warn Lim.
The measured gas temperature is outside the set warning limit values.
The warning limits can be adjusted using the configuration program "enSuite".
p Warn Lim..
The measured gas pressure is outside the set warning limit values.
The warning limits can be adjusted using the configuration program "enSuite".
z Warning
The sum of the gas analysis values for AGA-8 DC92 is more or less than 100%. An
accurate calculation of the real gas factor and the compressibility ratio factor can
therefore not be carried out.
Update error
Before the software update, an error was detected in the cached software image.
Softw. error
This message is used for factory diagnosis.
Please contact Elster support.
The programing of the device has generated an unusable combination of settings.
Sett. error
Please contact Elster support.
I2 Warn.sig.
If an input has been configured as a warning input, this message will be displayed if
an active signal appears at the corresponding terminal (e.g. terminal DE2).
I3 Warn.sig.
The input configuration can be adjusted using the configuration program "enSuite".
I4 Warn.sig.
I5 Warn.sig.
I6 Warn.sig.
T2 Warn Lim.
The measured gas temperature of the second sensor is outside the set warning limit
values.
The warning limits can be adjusted using the configuration program "enSuite".
p2 Warn Lim.
The measured gas pressure of the second sensor is outside the set warning limit
values.
The warning limits can be adjusted using the configuration program "enSuite".
Batt. low
The remaining battery power is less than six months.
The batteries need to be changed soon.
c) Remarks:
TA Warn Lim.
The measured ambient temperature is outside the set warning limit values.
The warning limits can be adjusted using the configuration program "enSuite".
Repair mode
The device is in revision mode.
Clock n. set
The internal clock of the volume corrector has not been adjusted at the factory.
Encoder err.
No volume at measurement conditions was recorded at the connected encoder on
input 1 for 20 seconds (with external power supply) or for one measurement cycle +
1 second (battery powered).
CDL full
The certification data log is full. Changing the parameters marked with "CDL"
without a calibration lock is only possible if the content of the certification data log
has been deleted.
U.Logb. full
The software update log is full. An update is only possible if the content of the
software update log has been deleted.
online
Data is currently being transmitted via an interface (modem, optical interface or
terminal interface).
If this message is displayed, the "o" will flash in the "Status" field of the display
Application Manual
70