Infilex ZM (Infilex: named for "Infinity" and "Flexible") Model
WY5122, integrated into savic-net FX
management system), manages remote units (also called
sub-controllers), such as Infilex VC, Infilex FC, and Infilex
SC.
Up to 50 remote units can be connected. Infilex ZM can
control these units separately as well as per group.
Infilex ZM communicates with the savic-net
through the transmission trunk line NC-bus and with the
remote units through the transmission trunk line SC-bus.
Features
Compact design:
Small size body ensures space saving.
Installation:
A quick-fit screwless (clamp) terminal block is used for
the communication terminal block of the I/O module,
ensuring the labor saving of the wiring work.
Additionally, either DIN rail mounting or screw mounting
can be selected.
Management of remote units:
Infilex ZM manages up to 50 connected remote units
(Infilex VC, Infilex FC, Infilex SC, etc.), allowing ON/OFF,
failure monitoring, measuring, and setting individually
from the BMS center unit. Infilex ZM can perform such
managements of remote units by group and is applicable
to any group configuration consisting of up to 50 units of
Infilex VC and Infilex FC.
provides flexible management.
ON/OFF can be commanded even when individual
measuring is commanded.
Risk diversification and high-speed supervision:
Infilex ZM has 50 programs of time schedules, analog
alarm monitoring, and runtime/cycle-count integrating in
order to manage the connected Infilex VC, Infilex FC,
Infilex SC, etc. This achieves diversification of risks and
high-speed supervision of BMS.
Azbil Corporation's controller Infilex series: Infilex is named for "Infinity" and "Flexible".
Infilex
Zone Manager
Model WY5122
BMS (building
FX center unit
Additionally, Infilex ZM
For example, group
1
ZM
One Infilex ZM controls up to 4 sets of VAV (VAV:
variable air volume, controlled by Infilex VC) and AHU
(controlled by Infilex GC). Load reset control of supply
air temperature, fan speed control, interlocking operation
are available. Additionally, the mixing loss control of the
interior VAV and perimeter FCU (fan coil unit) can be
performed.
Support functions:
Infilex ZM supports to adjust VAV by setting the
max./min. air volume levels of all VAV units included in a
specified set.
Infilex ZM also supports to adjust
AHU/FCU flow rate and to flush the piping by fully
opening and closing all the valves that the Infilex ZM
controls.
CE Marking certified product:
Infilex ZM Model WY5122W0000 (NC-bus model (Line
A)) conforms to all the applicable standards of CE
Marking (Class A).
AB-6439
Specifications/Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Infilex ZM WY5122 and is the answer not in the manual?

Questions and answers

Summary of Contents for Azbil Infilex ZM WY5122

  • Page 1 Infilex VC, Infilex FC, Infilex SC, etc. This achieves diversification of risks and high-speed supervision of BMS.  Azbil Corporation’s controller Infilex series: Infilex is named for “Infinity” and “Flexible”.
  • Page 2: Safety Instructions

    This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil Corporation’s sales representative.
  • Page 3: System Configurations

    AB-6439 System Configurations Client PC  BACnet NC-bus* (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)  Other connectable units to NC-bus: DIF/DIF-II/BMIF/energy meter  Infilex Note that the number of units to be connected must satisfy the following formula. Model WY5117C (Infilex ZM + DIF + DIF-II + BMIF) ...
  • Page 4: Basic Specifications

    AB-6439 Specifications Basic specifications Item Specification Rated voltage 100 V AC to 240 V AC, 50 Hz/60 Hz Allowable voltage 85 V AC to 264 V AC, 50 Hz/60 Hz range Power shutdown Power supply 80 V AC or less detection 35 VA Power consumption...
  • Page 5 AB-6439 Wiring specifications Item Wiring Wiring length Condition   Power supply JIS IV2.0 mm or JIS CVV 2.0 mm or greater  Ground resistance: 100  or lower Ground JIS IV 2.0 mm or JIS CVV 2.0 mm or greater ...
  • Page 6 AB-6439 Dimensions NC-bus SC-bus ERR1 ERR2 H-MMI NC-bus POWER BATT. Stripping Length Figure 3. Dimensions (mm)
  • Page 7: Parts Identification

    AB-6439 Parts Identification NC-bus SC-bus LED for operating status ERR1 ERR2 S1 switch* H-MMI Power switch Connector (female) for Data Setter NC-bus LED for power POWER  Do not press S1 switch. ON/OFF BATT. Battery holder DIN rail mounting hook Stripping Length Figure 4.
  • Page 8 AB-6439 Mounting Dimensions DIN rail mounting Mount and fix Infilex ZM on DIN rail so that it does not fall from the DIN rail. Fasten the bilateral sides of Infilex ZM with two DIN rail mounting brackets (Part No. 83104567-001, separate order is required). (60) Duct DIN rail...
  • Page 9 AB-6439 System indication label for the controller number Wiring The indication tag has the system indication label on its Wiring from power supply to terminal block back. Attach the crimp terminals for the M3 screw terminal Turn it over and fill in the controller number on the label. block to the wire ends, and connect them to the terminal block.
  • Page 10 AB-6439 Maintenance (Lithium Battery Replacement) Replace the lithium battery for backup (Part No. 83104934-001) every 5 years. IMPORTANT:  Only authorized service personnel is allowed to replace the battery.  Do not touch the power supply unit when replacing the battery. ...
  • Page 11: Precautions For Use

    AB-6439 Precautions for Use  Do not mount the product under the conditions of high temperature and humidity.  Do not drop the product.  For the wire replacement, be sure to shut down the power. (Disconnect the wiring between the power supply and the product power terminals.) ...
  • Page 12 AB-6439 Specifications are subject to change without notice. Building Systems Company http://www.azbil.com/ Rev.8.0 Sep. 2015 AB-6439 H (W03) (J: AI-6439 Rev. 4.2) Printed in Japan.