Dimensions And Required Minimum Space For Installation And Service (Eairc-Ms Type) - Panasonic EAIRC-MJ Series Installation Instructions Manual

Vrf system air conditioner for refrigerant r410a, for indoor/outdoor units
Table of Contents

Advertisement

3-2.
Dimensions and Required Minimum Space for
Installation and Service (EAIRC-MS Type)
This air conditioner (air curtain) is usually installed freely
suspended from the ceiling.
● The ceiling must be strong enough to support the weight of
the unit.
● The recommended installation height for this Air Curtain type
is 2.4 m for worst conditions or 2.7 m for medium conditions
or 3.0 m for optimum conditions and depending on the site
conditions should not be exceeded.
● The unit should be installed as close as possible to the wall
and as flush as possible to the top of the door.
● The air flow outlet should be free and not obstructed in any
way.
● The unit should be accessible over the whole length of the
unit at any time.
● The inspection cover should be accessible over the whole
length of the unit at any time.
It is recommended that space be provided (600 × 600 mm)
for checking and servicing the electrical system.
Fig. 3-2 shows the detailed dimensions of the indoor unit.
Top view
Rivet nuts M8
75
45
Liquid pipe
Suction pipe
60
100
Front view
105
Box for customer PCB
30
Bottom view
70
A
A+210
Empty box
Inlet grille
25
Side view
45
35 295
460
105
Section
260
8
Rivet nuts M5
Space for
customer PCB
Conduit
holes
100
30
Unit: mm
Fig. 3-2