3-2.
Dimensions and Required Minimum Space for
Installation and Service (EAIRC-MS Type)
This air conditioner (air curtain) is usually installed freely
●
suspended from the ceiling.
● The ceiling must be strong enough to support the weight of
the unit.
● The recommended installation height for this Air Curtain type
is 2.4 m for worst conditions or 2.7 m for medium conditions
or 3.0 m for optimum conditions and depending on the site
conditions should not be exceeded.
● The unit should be installed as close as possible to the wall
and as flush as possible to the top of the door.
● The air flow outlet should be free and not obstructed in any
way.
● The unit should be accessible over the whole length of the
unit at any time.
● The inspection cover should be accessible over the whole
length of the unit at any time.
It is recommended that space be provided (600 × 600 mm)
●
for checking and servicing the electrical system.
Fig. 3-2 shows the detailed dimensions of the indoor unit.
●
Top view
Rivet nuts M8
75
45
Liquid pipe
Suction pipe
60
100
Front view
105
Box for customer PCB
30
Bottom view
70
A
A+210
Empty box
Inlet grille
25
Side view
45
35 295
460
105
Section
260
8
Rivet nuts M5
Space for
customer PCB
Conduit
holes
100
30
Unit: mm
Fig. 3-2