IMPORTANT
— Each 3-wire (SPDT) actuator must have individual
SPDT controller.
— On 24V systems, never jumper the valve coil
terminals, even temporarily. This may damage the
thermostat.
— The cable version must be used for mixed line voltage
and 24 Vac (Safety Extra Low Voltage) applications.
For controller action and electrical terminations, see Tables A
and B.
Figs. 7 and 8 show wiring diagrams as printed on product label
for the Cable Model and Molex™ Model for use with SPDT
controller.
Figs. 9 and 10 show wiring connections with SPDT and SPST
controllers. Port “A” open and closed denote valve open and
closed positions respectively. On auxiliary switch models,
terminal 4 (grey wire) contact makes at the end of the port A
opening stroke. On Molex™ connector models, valve and
auxiliary switch voltage must be the same to meet approval
requirement.
Table A. Electrical Termination - ‘Colours & Pin Numbers’
Actuator
Type
Cable Models
Molex™ Models
3-Way Valve
3-Wire
Blue & Brown energised
Pin# 2 & 3 energised
Stem up
(for SPDT
(Black de-energised)
Pin# 6 de-energised
(A port closes)
Controller)
Blue & Black energised
Pin# 2 & 6 energised
Stem down
(Brown de-energised)
Pin # 3 de-energised
(B port closes)
2-Wire +
Blue & Brown energised
Pin# 2 & 3 energised
Stem up
COM (for
(Brown & Black open)
Pin# 3 & 6 open
(A port closes)
SPST
Blue & Brown energised
Pin# 2 & 3 energised
Stem down
Controller)
(Brown & Black closed)
Pin# 3 & 6 closed
(B port closes)
Table B. Electrical Termination- ‘Contacts Function’
Molex™ Models
Cable Models
Terminal
Action
Wire Colour
(See Fig. 7)
(See Fig. 8)
Actuator
Brown
3
A - Closed
Black
6
A - Open
Blue
2
Common
Auxiliary
White
5
NC
switch
Orange
1
COM
(optional)
Grey
4
NO
COLLEGAMENTI ELETTRICI
ATTENZIONE
L’installazione elettrica, come pure i cavi ed i
relativi accessori devono essere conformi alle
direttive ce ed alle normative cei.
IMPORTANTE:
— Ciascun attuatore per comando a 3 fili (SPDT) deve
essere comandato dal contatto SPDT di un solo
regolatore.
— Nei modelli a 24V, non cortocircuitare, neanche
temporaneamente, la bobina del motore. Potrebbe
danneggiarsi il termostato.
— Utilizzano una tensione differente tra motore e micro
ausiliario (es. 24V e 230V ca) è necessario utilizzare
la sola versione con cavo da 1 metro (Sicurezza a
bassa tensione).
Per l’azione del regolatore ed i morsetti elettrici riferirsi alle
tabelle A, B.
Page 6