Installation

The LyteScene II Touch Screen is available in two mounting configurations: wall-mount, surface or
flush (ILSCLTSII) and rack-mount (ILSCLTSIIRM). Refer to appropriate installation method below.
The Lytemode ILS Network consists of a single CAT5e cable connecting all ILS devices in a daisy
chain manner. All units connect to the network using a 9-pin connector (included).

ILSCLTSII (Wall-Mount)

To install wall-mount unit:
Step 1. Unpack ILSCLTSII Touch Screen and inspect for any signs of shipping damage.
Step 2. Route ILS network cable through appropriate knock-out hole and install rough-in
box (sold separately) into wall (Figure 1).
Step 3. Connect ILS network cable to Touch Screen ILS connector.
Step 4. Install Touch Screen onto rough-in box using four #6 flat head screws.
From ILS Network
Knock-Out Hole
Surface
Mounting
Hole (4)
Rough-In Box
(Part # ILSCLBTSII,
Sold Separately)
Touch Screen Assembly
(Wall-Mount Version)
Figure 1: Installing ILSCLTSII Wall-Mount Touch Screen
U
'
G
SER
S
UIDE
TOP VIEW
ILS 9-Pin
Connector
PIN
1
2
3
4
5
6
7
8
9
#6 Flat Head Screw (4)
WARNING!
Remove power from house service before connecting
any wiring or cables to the LyteScene II Touch Screen.
ILS Network
Connection
I
NSTALLATION
SIGNAL
WH/OR (+ Data)
OR (- Data)
SHIELD
WH/GN (+ Volts)
GN (Ground)
WH/BL (+ Volts)
BL (Ground)
WH/BR (+ Volts)
BR (Ground)
All other connectors are not
applicable to this installation