Download Print this page

Siemens SINAMICS G110D Series Getting Started page 25

Distributed converter
Hide thumbs

Advertisement

SINAMICS G110D model no.
6SL3511-.PE24-0AM.
6SL3511-.PE25-5AM.
6SL3511-.PE27-5AM.
Table 3- 10
Type E combination motor controllers (NKJH) for group installation
SINAMICS G110D
model no.
6SL3511-.PE17-5AM.
6SL3511-.PE21-5AM.
6SL3511-.PE23-0AM.
6SL3511-.PE24-0AM.
6SL3511-.PE25-5AM.
6SL3511-.PE27-5AM.
*Where "_" in the CMC model no. can be replaced by "1" or "2".
Listed (NKJH) Siemens CMCs of the same type with a current rating lower than that
specified in the table, corresponding to SINAMICS G110D drive model number and with a
voltage rating of at least 480 V AC may also be used.
SINAMICS G110D
Getting Started, 07/2016, FW V3.63, A5E38556288B AA
Max current rating of circuit
breaker (A)
30
30
30
CMC model no.*
Max. rated cur-
3RV2021-4DA..
3RV_031-4DA..
3RV2021-4DA..
3RV_031-4DA..
3RV2021-4DA..
3RV_031-4DA..
3RV2021-4DA..
3RV_031-4DA..
3RV2021-4DA..
3RV_031-4DA..
3RV2021-4DA..
3RV_031-4DA..
Circuit breaker types
3RV1742
3RV2721
LGG
CED6
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
Rated hp at 460 V
rent (A)
AC
25
15
25
20
25
15
25
20
25
15
25
20
25
15
25
20
25
15
25
20
25
15
25
20
Electrical Installation
3.1 SINAMICS G110D Specifications
SINAMICS G110D SCCR for
group installation using cir-
cuit breakers
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
SINAMICS G110D SCCR for
group installation using CMC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
25