Electrical Installation
3.1 SINAMICS G110D Specifications
Table 3- 7
Branch circuit protection with Type E combination motor controllers (NKJH)
SINAMICS G110D
model no.
6SL3511-.PE17-5AM.
6SL3511-.PE21-5AM.
6SL3511-.PE23-0AM.
6SL3511-.PE24-0AM.
6SL3511-.PE25-5AM.
6SL3511-.PE27-5AM.
*Where "_" in the CMC model no. can be replaced by "1" or "2".
Table 3- 8
SINAMICS G110D model no.
Table 3- 9
Circuit breakers (DIVQ) for group installation
SINAMICS G110D model no.
6SL3511-.PE17-5AM.
6SL3511-.PE21-5AM.
6SL3511-.PE23-0AM.
24
CMC model no.*
3RV20_1-1JA..
3RV20_1-1JA..
3RV2021-4AA..
3RV1031-4AA..
3RV2021-4CA..
3RV_031-4BA..
3RV2021-4DA..
3RV_031-4DA..
3RV_031-4EA..
Non-semiconductor fuses (JDDZ) for group installation
6SL3511-.PE17-5AM.
6SL3511-.PE21-5AM.
6SL3511-.PE23-0AM.
6SL3511-.PE24-0AM.
6SL3511-.PE25-5AM.
6SL3511-.PE27-5AM.
Max current rating of circuit
breaker (A)
30
30
30
Max. rated
Rated hp at 460 V
current (A)
AC
10
5
10
5
16
10
16
10
22
15
20
15
25
15
25
20
32
25
Max. current rating of fuse (A)
30
Circuit breaker types
3RV1742
3RV2711
LGG
CED6
3RV1742
3RV2711
LGG
CED6
3RV1742
3RV2721
LGG
CED6
Getting Started, 07/2016, FW V3.63, A5E38556288B AA
SINAMICS G110D SCCR with
CMC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 Y / 277 V AC
SINAMICS G110D SCCR for
group installation using fuse
65 kA , 480 V AC
SINAMICS G110D SCCR for
group installation using cir-
cuit breakers
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC