Programming Guide
®
VLT
AutomationDrive FC 301/302
www.danfoss.com/drives

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss VLT AutomationDrive FC 301

  • Page 1 MAKING MODERN LIVING POSSIBLE Programming Guide ® AutomationDrive FC 301/302 www.danfoss.com/drives...
  • Page 3: Table Of Contents

    ® Contents AutomationDrive FC 301/302 Programming Guide Contents 1 Introduction 1.1 Software Version 1.2 Approvals 1.3 Symbols 1.4 Definitions 1.4.1 Frequency Converter 1.4.2 Input 1.4.3 Motor 1.4.4 References 1.4.5 Miscellaneous 1.5 Safety 1.6 Electrical Wiring 1.6.1 Electrical Wiring - Control Cables 2 How to Programme 2.1 The Graphical and Numerical Local Control Panels 2.1.1 The LCD-Display...
  • Page 4: Parameters: 18-** Data Readouts

    ® Contents AutomationDrive FC 301/302 Programming Guide 3.6 Parameters: 4-** Limits/Warnings 3.7 Parameters: 5-** Digital In/Out 3.8 Parameters: 6-** Analog In/Out 3.9 Parameters: 7-** Controllers 3.10 Parameters: 8-** Communications and Options 3.11 Parameters: 9-** Profibus 3.12 Parameters: 10-** DeviceNet CAN Fieldbus 3.13 Parameters: 12-** Ethernet 3.14 Parameters: 13-** Smart Logic Control 3.15 Parameters: 14-** Special Functions...
  • Page 5: Introduction

    Introduction ® AutomationDrive FC 301/302 Programming Guide 1 Introduction VLT,MAX Maximum output voltage. 1.1 Software Version 1.4.2 Input Programming Guide Software version: 7.X Control command Start and stop the connected motor by means of LCP and This Programming Guide can be used for all FC 300 frequency digital inputs.
  • Page 6: References

    Introduction ® AutomationDrive FC 301/302 Programming Guide Rated torque (motor). Determines the relationship between the reference input at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting reference. The minimum reference value set in Instantaneous motor voltage. 3-02 Minimum Reference.
  • Page 7 Introduction ® AutomationDrive FC 301/302 Programming Guide Smart Logic Control (SLC) The Local Control Panel makes up a complete interface for The SLC is a sequence of user-defined actions executed control and programming of the frequency converter. The when the associated user-defined events are evaluated as control panel is detachable and can be installed up to 3 m true by the Smart Logic Control.
  • Page 8: Safety

    Introduction ® AutomationDrive FC 301/302 Programming Guide The power factor indicates to which extent the frequency Warning against unintended start converter imposes a load on the mains supply. The motor can be stopped with digital The lower the power factor, the higher the I for the commands, bus commands, references or a local same kW performance.
  • Page 9 Introduction ® AutomationDrive FC 301/302 Programming Guide WARNING Protection Mode Once a hardware limit on motor current or DC link voltage High Voltage is exceeded the frequency converter enters the Protection Touching the electrical parts may be fatal - even after mode.
  • Page 10: Electrical Wiring

    Introduction ® AutomationDrive FC 301/302 Programming Guide 1.6 Electrical Wiring 1.6.1 Electrical Wiring - Control Cables 91 (L1) (U) 96 3 Phase (V) 97 92 (L2) power (W) 98 93 (L3) input (PE) 99 Motor Switch Mode 88 (-) DC bus Power Supply 89 (+) 10Vdc...
  • Page 11 Introduction ® AutomationDrive FC 301/302 Programming Guide The digital and analog inputs and outputs must be connected separately to the common inputs (terminal 20, 55, 39) of the frequency converter to avoid ground currents from both groups to affect other groups. For example, switching on the digital input may disturb the analog input signal.
  • Page 12 Introduction ® AutomationDrive FC 301/302 Programming Guide 1.6.3 Pulse Start/Stop +24V Terminal 18 = 5-10 Terminal 18 Digital Input, [9] Latched start. Par. 5-10 Terminal 27= 5-12 Terminal 27 Digital Input, [6] Stop inverse. Terminal 37 = Safe Torque Off (where available). Par.
  • Page 13: How To Programme

    How to Programme ® AutomationDrive FC 301/302 Programming Guide 2 How to Programme 2.1 The Graphical and Numerical Local Control Panels Status 1(0) The easiest programming of the frequency converter is 1234rpm 10,4A 43,5Hz performed by the Graphical LCP (LCP 102). Consult the frequency converter Design Guide, when using the Numeric Local Control Panel (LCP 101).
  • Page 14: The Lcd-Display

    How to Programme ® AutomationDrive FC 301/302 Programming Guide 2.1.1 The LCD-Display The LCD-display has backlight and a total of 6 alpha- numeric lines. The display lines show the direction of rotation (arrow), the selected set-up as well as the programming set-up.
  • Page 15: Quick Transfer Of Parameter Settings Between Multiple Frequency Converters

    How to Programme ® AutomationDrive FC 301/302 Programming Guide [OK]. Information is displayed about the condition of the External stop signals activated with control signals or a frequency converter before it enters the alarm mode. serial bus override a “start” command via the LCP. The following control signals are still active when [Hand [Back] On] is activated...
  • Page 16: Display Mode

    How to Programme ® AutomationDrive FC 301/302 Programming Guide 2.1.4 Display Mode - Selection of Read- Outs Alarm Quick Main Status Menu Menu It is possible to toggle between three status read-out screens by pressing [Status]. Operating variables with different formatting are shown in each status screen - see below.
  • Page 17: Parameter Set-Up

    How to Programme ® AutomationDrive FC 301/302 Programming Guide Operating variable Unit Status 1 (1) 16-63 Terminal 54 Switch Setting 207RPM 5.25A 24.4 kW 16-64 Analog Input 54 16-65 Analog Output 42 [mA] [mA] 16-66 Digital Output [bin] [bin] 16-67 Pulse Input #29 [Hz] [Hz] Auto Remote Running 16-68 Freq.
  • Page 18: Initial Commissioning

    How to Programme ® AutomationDrive FC 301/302 Programming Guide * If terminal 27 is set to [0] no function, no connection to 0RPM 0.00A 1(1) +24 V on terminal 27 is necessary. Quick Menus Q1 My Personal Menu Select Changes made to get information about: Q2 Quick Setup Q4 Smart Setup •...
  • Page 19 How to Programme ® AutomationDrive FC 301/302 Programming Guide 1-23 Motor Frequency Set Nameplate frequency 1-24 Motor Current Set Nameplate current 1-25 Motor Nominal Speed Set Nameplate speed in RPM If terminal default is Coast inverse it is possible to change 5-12 Terminal 27 Digital Input this setting to No function.
  • Page 20: Main Menu Mode

    How to Programme ® AutomationDrive FC 301/302 Programming Guide Another easy way of commissioning the frequency All parameters can be changed in the Main Menu. converter is by using the Smart Application Set-up (SAS), However, depending on the choice of configuration which can also be found under the Quick Menu.
  • Page 21: Changing Data

    How to Programme ® AutomationDrive FC 301/302 Programming Guide 2.1.10 Changing Data 729RPM 6.21A 1(1) Load depen. setting 1- 6* The procedure for changing data is the same in the Quick 1 - 60 Low speed load menu and the Main menu mode. Press [OK] to change the compensation selected parameter.
  • Page 22 How to Programme ® AutomationDrive FC 301/302 Programming Guide ▲ ▼ Select the parameter, press [OK], and use [ ] to scroll through the indexed values. To change the parameter value, select the indexed value and press [OK]. Change the ▲...
  • Page 23: Lcp Keys

    How to Programme ® AutomationDrive FC 301/302 Programming Guide A 17 [Hand On] enables control of the frequency converter via the LCP. [Hand On] also starts the motor and it is now possible to enter the motor speed data with the arrow keys. The key Setup 1 can be selected as [1] Enable or [0] Disable via 0-40 [Hand Illustration 2.23 Alarm...
  • Page 24 How to Programme ® AutomationDrive FC 301/302 Programming Guide Press [OK] Disconnect the mains supply and wait until the display turns off. Reconnect the mains supply - the frequency converter is now reset. 14-22 Operation Mode initialises all except: 14-50 RFI Filter 8-30 Protocol 8-31 Address 8-32 FC Port Baud Rate...
  • Page 25: Parameter Descriptions

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3 Parameter Descriptions 15-** Drive information parameters 3.1 Parameter Selection 16-** Readout parameters Parameters for FC 300 are grouped into various parameter groups for easy selection of the correct parameters for 17-** Encoder Option parameters optimised operation of the frequency converter.
  • Page 26: Parameters: 0-** Operation And Display

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.2 Parameters: 0-** Operation and Display 0-01 Language Option: Function: Parameters related to the fundamental functions of the [51] Bahasa Part of Language package 2 frequency converter, function of the LCP keys and configu- Indonesia ration of the LCP display.
  • Page 27 Option: Function: Select the set-up to control the frequency converter functions. Factory Cannot be changed. It contains the Danfoss setup data set, and can be used as a data source when returning the other set-ups to a known state. Set-up 1...
  • Page 28 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Set-up 0-12 This Set-up Linked to Option: Function: 2 are synchronised (or ‘linked’). Synchronisation P 0-11 can be performed in 2 ways: 1. Change the edit set-up to [2] Set-up 2 in 0-11 Edit Set-up and set 0-12 This Set-up Linked to to [1] Set-up 1.
  • Page 29 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 0-13 Readout: Linked Set-ups 0-20 Display Line 1.1 Small Option: Function: Array [5] Range: Function: Select a variable for display in line 1, left position. [0 - View a list of all the set-ups linked by means of 255 ] 0-12 This Set-up Linked to.
  • Page 30 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Function: Option: Function: [1616] Torque [Nm] Actual motor torque in Nm [1648] Speed Ref. After Ramp [RPM] [1617] Speed [RPM] Speed in RPM (revolutions per [1650] External Reference Sum of the external reference...
  • Page 31 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Function: Option: Function: [1672] Counter A Application dependent (e.g. [1891] Process PID Output SLC Control) [1892] Process PID Clamped Output [1673] Counter B Application dependent (e.g.
  • Page 32 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 0-20 Display Line 1.1 Small 0-25 My Personal Menu Option: Function: Range: Function: [9914] Paramdb requests in Size [0 - Define up to 50 parameters to appear in the queue related 9999 ] Q1 Personal Menu, accessible via the [Quick [9917] tCon1 time...
  • Page 33 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Unit Type Speed Relation 0-30 Unit for User-defined Readout Dimensionless Option: Function: Speed [124] CFM Flow, volume [125] ft³/s Flow, mass Linear [126] ft³/min Velocity [127] ft³/h Length [130] lb/s Temperature [131] lb/min Pressure Quadratic [132] lb/h...
  • Page 34 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 0-38 Display Text 2 0-42 [Auto on] Key on LCP Range: Function: Option: Function: [0 - Enter a text which can be viewed in the graphical [2] Password Avoids unauthorised start in Auto mode. If display by selecting [38] Display Text 2 in 0-42 [Auto on] Key on LCP is included in the Quick 0-20 Display Line 1.1 Small, 0-21 Display Line 1.2...
  • Page 35 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide If Full access [0] is selected then 0-60 Main Menu Password, 0-50 LCP Copy 0-65 Personal Menu Password and 0-66 Access to Personal Option: Function: Menu w/o Password is ignored. Data from LCP to NOTICE Safety Par.
  • Page 36: Parameters: 1-** Load And Motor

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.3 Parameters: 1-** Load and Motor 1-01 Motor Control Principle Option: Function: 3.3.1 1-0* General Settings NOTICE This parameter cannot be adjusted Define whether the frequency converter operates in speed while the motor is running. mode or torque mode;...
  • Page 37 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-02 Flux Motor Feedback Source 1-04 Overload Mode Option: Function: Option: Function: Encoder interface 1 of the optional Use this parameter to configure the frequency converter for either High or Normal overload. Encoder 1 programmable motion controller MCO 305.
  • Page 38 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-59 Flystart Test Pulses Frequency 1-07 Motor Angle Offset Adjust 1-70 PM Start Mode This parameter is only valid for FC 302 and only in combination with a PM motor with feedback. 30-20 High Starting Torque Time [s] Range: Function:...
  • Page 39 1-10 Motor Construction. Enter 3.3.4 1-2* Motor Data motor parameter manually. [10] Danfoss OGD Selectable when [1] PM, non salient SPM is This parameter group contains input data from the LA10 selected in 1-10 Motor Construction. Only nameplate on the connected motor.
  • Page 40 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-20 Motor Power [kW] 1-26 Motor Cont. Rated Torque Range: Function: Range: Function: This parameter is visible in LCP if Size [0.1 - Enter the value from the motor 0-03 Regional Settings is [0] International. related 10000 nameplate data.
  • Page 41 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide • For the best adaptation of the frequency P 1-34 P 1-33 P 1-30 converter, run AMA on a cold motor. 1δ 2δ • AMA cannot be performed while the motor is running.
  • Page 42 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-33 Stator Leakage Reactance (X1) 1-35 Main Reactance (Xh) Range: Function: Range: Function: Size [ 0.0400 - Set the stator leakage reactance of the measures the value from the motor. related 400.0000 motor using one of these methods: Ohm] Run an AMA on a cold motor.
  • Page 43 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Poles @ 50 Hz @ 60 Hz 1-44 d-axis Inductance Sat. (LdSat) 2700-2880 3250-3460 Range: Function: 1350-1450 1625-1730 Size related [0 - This parameter corresponds to the 1000 inductance saturation of Ld. Ideally; this 700-960 840-1153 parameter has the same value as 1-37 d-...
  • Page 44 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-48 Inductance Sat. Point 1-52 Min Speed Normal Magnetising [Hz] Range: Function: Range: Function: 35 % [1 - 500 %] Inductance Saturation Point. for 1-50 Motor Magnetisation at Zero Speed. 3.3.6 1-5* Load Indep. Setting 1-53 Model Shift Frequency Range: Function:...
  • Page 45 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-53 Model Shift Frequency Motor Voltage Par 1-55 [x] Range: Function: x 0.1 x 0.125 1-55[5] 1-55[4] Variable current Flux model 2 1-55[3] model P 1-53 1-55[2] Illustration 3.9 1-00 Configuration Mode = 1-55[1] [0] Speed open loop, 1-01 Motor Control 1-55[0]...
  • Page 46 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-60 Low Speed Load Compensation 1-63 Slip Compensation Time Constant Range: Function: Range: Function: frequency range within which this parameter is Size related [0.05 - Enter the slip compensation reaction active. 5 s] speed.
  • Page 47 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.3.8 1-7* Start Adjustments 1-66 Min. Current at Low Speed Range: Function: parameter with the highest value adjusts 1-70 PM Start Mode 1-66 Min. Current at Low Speed. The current setting in 1-66 Min. Current at Low Speed is Select the PM motor start-up mode.
  • Page 48 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide NOTICE 1-72 Start Function Option: Function: This function is not recommended for hoisting applications. Horizontal Only possible with VVC plus For power levels above 55 kW, flux mode must be operation For obtaining the function described in used to achieve the best performance.
  • Page 49 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 1-80 Function at Stop 1-82 Min Speed for Function at Stop [Hz] Option: Function: Range: Function: Coast Leaves motor in free mode. The motor is Size related [ 0 - 20.0 Set the output frequency at which disconnected from the frequency converter.
  • Page 50 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.3.10 1-9* Motor Temperature 1-83 Precise Stop Function Option: Function: This reset function can for example be used to 1-90 Motor Thermal Protection compensate for the extra distance done during ramping down and to reduce the impacts of Option: Function: gradual wear of mechanical parts.
  • Page 51 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Using a digital input and 10 V as power supply: 1-90 Motor Thermal Protection Example: The frequency converter trips when the motor Option: Function: temperature is too high. and if the frequency converter trips (thermal Parameter set-up: warning).
  • Page 52 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Resistance (Rr)) for asynchronous motors, depending on t [s] winding temperature. The calculation is: 2000 where Rs = Rs 20° C x (1 + α cu x Δ T ) Ω α cu = 0.00393 1000 KTY sensors can be used for motor protecting (1-97 KTY...
  • Page 53 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Function Setting 1-90 Motor Thermal [20] ATEX ETR 12 13 18 33 20 Protection 1-94 ATEX ETR cur.lim. speed reduction 1-98 ATEX ETR interpol. points freq. PTC / Thermistor <6.6 k Ω >10.8 k Ω Motor name plate 1-99 ATEX ETR interpol Illustration 3.17 Thermistor Connection...
  • Page 54 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide NOTICE 1-98 ATEX ETR interpol. points freq. FC 302 only. Digital input should be set to [0] PNP - Only visible if 1-90 Motor Thermal Protection is set to [20]. Active at 24 V in 5-00 Digital I/O Mode. Range: Function: 1-94 ATEX ETR cur.lim.
  • Page 55: Parameters: 2-** Brakes

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Together with 1-98 ATEX ETR interpol. points freq., these Application Settings make up a table (f [Hz],I [%]). Low inertia applications 1-17 Voltage filter time const. to be <5 increased by factor 5 to 10 Load Motor NOTICE...
  • Page 56 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 2-00 DC Hold Current 2-04 DC Brake Cut In Speed [Hz] Range: Function: Range: Function: 50 % [ 0 - Enter a value for holding current as a percentage Size related [ 0 - Set the DC brake cut-in speed for of the rated motor current I set in 1-24 Motor...
  • Page 57 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 2-10 Brake Function 2-13 Brake Power Monitoring Option: Function: Option: Function: the OVC-function. Increasing the electrical losses in This parameter is only active in frequency the motor allows the OVC function to increase the converters with an integral dynamic brake.
  • Page 58 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide NOTICE 2-15 Brake Check Option: Function: OVC must not be enabled in hoisting applications. If the DC-link ripple amplitude while braking is lower than the DC link ripple amplitude 2-18 Brake Check Condition before braking + 1%: Brake check has failed Range: Function:...
  • Page 59 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Start 1=on term.18 Par 1-71 Start delay time Par 2-21 Activate brake speed Shaft speed Par 1-74 Start speed Output current Pre-magnetizing current or DC hold current Par 2-20 Par 1-76 Start current/ Release brake current Par 2-00 DC hold current Par 2-23...
  • Page 60 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide frequency converters are connected to the same 2-25 Brake Release Time shaft. Range: Function: • No ramp up until feedback confirms mechanical 0.20 s [0 - 5 This value defines the time it takes for the brake is open.
  • Page 61 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Parameters 2-26 to 2-33 are only available for the hoist 2-32 Speed PID Start Integral Time mechanical brake control (FLUX with motor feedback). Range: Function: 200.0 ms [1.0 - 20000.0 ms] 2-26 Torque Ref 2-33 Speed PID Start Lowpass Filter Time Range: Function:...
  • Page 62: Parameters: 3-** Reference/Ramps

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.5 Parameters: 3-** Reference/Ramps 3-01 Reference/Feedback Unit Option: Function: Parameters for reference handling, definition of limitations, [60] °C and configuration of the reaction of the frequency [70] mbar converter to changes. [71] [72] 3.5.1 3-0* Reference Limits [73]...
  • Page 63 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-03 Maximum Reference 12 (+24V) Range: Function: Preset 76543210 Size [ par. 3-02 - Enter the Maximum Reference. The 10101010 [P 5-13=Preset ref. bit 0] related 999999.999 Maximum Reference is the highest ReferenceFeed- value obtainable by summing all 11001100...
  • Page 64 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-13 Reference Site 3-15 Reference Resource 1 Option: Function: Option: Function: Select which reference site to activate. of these reference signals defines the actual reference. [0] Linked to Use local reference when in Hand mode; or Hand / remote reference when in Auto mode.
  • Page 65 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-17 Reference Resource 3 3-19 Jog Speed [RPM] Option: Function: Range: Function: [22] Analog input X30-12 See also 3-80 Jog Ramp Time. [29] Analog Input X48/2 3.5.3 Ramps 3-18 Relative Scaling Reference Resource 3-4* Ramp 1 Option: Function:...
  • Page 66 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-40 Ramp 1 Type 3-45 Ramp 1 S-ramp Ratio at Accel. Start Option: Function: Range: Function: A linear ramp gives constant acceleration sation achieved, and thus the lower the torque during ramping. An S-ramp gives non-linear jerks occurring in the application.
  • Page 67 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide NOTICE 3-57 Ramp 2 S-ramp Ratio at Decel. Start Range: Function: If [1] S-ramp Const Jerk is selected and the reference during ramping is changed the ramp time may be 50 % [ 1 - Enter the proportion of the total ramp-down prolonged to realise a jerk-free movement, which may...
  • Page 68 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.5.6 3-7* Ramp 4 3-61 Ramp 3 Ramp up Time Range: Function: Configure ramp parameters, see parameter group 3-4* ramp-down time in 3-62 Ramp 3 Ramp Ramp 1. down Time. 3-70 Ramp 4 Type 3-62 Ramp 3 Ramp down Time Option: Function:...
  • Page 69 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-75 Ramp 4 S-ramp Ratio at Accel. Start Range: Function: 50 % [ 1 - Enter the proportion of the total ramp-up time P 4-13 RPM 99 %] (3-71 Ramp 4 Ramp up Time) in which the high limit acceleration torque increases.
  • Page 70 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-82 Quick Stop Ramp Type Speed Option: Function: Select the ramp type, depending on P 3-95 requirements for acceleration and deceleration. A linear ramp gives constant Time (s) acceleration during ramping. An S-ramp gives non-linear acceleration, compensating for jerk in the application.
  • Page 71 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-95 Ramp Delay Range: Function: Size [ 0 - Enter the delay required from activation of related the digital potentiometer function until the frequency converter starts to ramp the reference. With a delay of 0 ms, the reference starts to ramp as soon as INCREASE/DECREASE is activated.
  • Page 72: Parameters: 4-** Limits/Warnings

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.6 Parameters: 4-** Limits/Warnings 4-13 Motor Speed High Limit [RPM] Range: Function: 3.6.1 4-1* Motor Limits Size related [ par. Enter the maximum limit for motor 4-11 - speed. The Motor Speed High Limit can Define torque, current and speed limits for the motor, and 60000 be set to correspond to the...
  • Page 73 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide NOTICE 4-20 Torque Limit Factor Source Option: Function: The torque limit reacts on the actual, non-filtrated torque, including torque spikes. This is not the torque [14] Analog in X30-12 that is seen from the LCP or the Fieldbus as that is [16] Analog in X30-12 filtered.
  • Page 74 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 4-30 Motor Feedback Loss Function 4-34 Tracking Error Function Option: Function: Option: Function: Switch to Open frequency that is sent to the motor (16-13 Frequency). Loop The reaction is activated, if the measured Select Setup 1 difference is more than specified in 4-35 Tracking Select Setup 2...
  • Page 75 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 4-39 Tracking Error After Ramping Timeout 4-52 Warning Speed Low Range: Function: Range: Function: [0 - 60 s] Enter the time-out period after ramping where 0 RPM [ 0 - Enter the n value.
  • Page 76: Parameters: 5-** Digital In/Out

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 4-57 Warning Feedback High 4-61 Bypass Speed From [Hz] Range: Function: Array [4] 999999.999 [ par. 4-56 - Enter the upper feedback Range: Function: ReferenceFeed- 999999.999 limit. When the feedback Size related [ 0 - par.
  • Page 77 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Digital input function Select Terminal 5-01 Terminal 27 Mode Pulse input Time Based [32] 29, 33 Option: Function: Ramp bit 0 [34] NOTICE Ramp bit 1 [35] This parameter cannot be adjusted Latched precise start [40] 18, 19...
  • Page 78 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3-81 Quick Stop Ramp Time. When motor [16] Preset ref Preset ref. bit 0,1, and 2 enables a choice stops, the shaft is in free mode. Logic ‘0’ ⇒ bit 0 between one of the 8 preset references Quick-stop.
  • Page 79 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide [22] Speed Same as [21] Speed up. frequencies, but is not as precise at higher down frequencies. This principle has a cut-off frequency which makes it unsuited for encoders [23] Set-up Select Set-up select bit 0 or Select Set-up select with very low resolutions (e.g.
  • Page 80 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide [56] DigiPot DECREASE signal to the Digital Potenti- 5-10 Terminal 18 Digital Input Decrease ometer function described in parameter Option: Function: group 3-9* Digital Pot. Meter Start Functions are described under parameter group 5-1* [57] DigiPot Clear Clears the Digital Potentiometer reference...
  • Page 81 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-18 Terminal X30/4 Digital Input Function Relay Option: Function: No Function This parameter is active when option module Safe Stop Alarm [1]* Safe Stop [A68] operation MCB 101 is installed in the frequency Safe Stop Warning Safe Stop [W68] converter.
  • Page 82 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 4-50 Warning Current Low to 4-53 Warning 5-24 Terminal X46/9 Digital Input Speed High. There are no warnings. Option: Function: Run on Motor runs at reference speed. No This parameter is active when option module reference / no warnings.
  • Page 83 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide [27] Torque limit Use in performing a coasting stop and in [62] Comparator 2 See parameter group 13-1* Comparators. and stop torque limit condition. If the frequency If Comparator 2 is evaluated as TRUE, the converter has received a stop signal and output goes high.
  • Page 84 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide The input goes low whenever the Smart indicated by the LED light above Auto Logic Action [36] Set dig. out. E low is On). executed. [151] ATEX ETR cur. Selectable, if 1-90 Motor Thermal [85] SL Digital See 13-52 SL Controller Action.
  • Page 85 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-32 Term X30/6 Digi Out (MCB 101) 5-32 Term X30/6 Digi Out (MCB 101) Option: Function: Option: Function: No operation This parameter is active when [62] Comparator 2 option module MCB 101 is [63] Comparator 3 mounted in the frequency...
  • Page 86 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-33 Term X30/7 Digi Out (MCB 101) 5-33 Term X30/7 Digi Out (MCB 101) Option: Function: Option: Function: Running [82] SL digital output C Running / no warning [83] SL digital output D Run in range/no warn [84] SL digital output E...
  • Page 87 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-40 Function Relay 5-40 Function Relay Array [9] Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
  • Page 88 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-40 Function Relay 5-40 Function Relay Array [9] Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
  • Page 89 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-40 Function Relay 5-40 Function Relay Array [9] Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
  • Page 90 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-40 Function Relay 5-41 On Delay, Relay Array [9] Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB [4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8]) 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] Range:...
  • Page 91 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.7.5 5-5* Pulse Input 5-52 Term. 29 Low Ref./Feedb. Value Range: Function: The pulse input parameters are used to define an Digital Input = applicable appropriate window for the impulse reference area by value).
  • Page 92 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide No operation 5-58 Term. 33 High Ref./Feedb. Value [45] Bus control Range: Function: [48] Bus control time-out Size related [-999999.999 - Enter the high reference [51] MCO controlled 999999.999 value [RPM] for the motor [100] Output frequency ReferenceFeed- shaft speed.
  • Page 93 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide encoder inputs when [1] 24 V encoder is selected in 5-63 Terminal 29 Pulse Output Variable 1-02 Flux Motor Feedback Source and 7-00 Speed PID Option: Function: Feedback Source. The encoder used is a dual channel (A [105] Torq relate to rated and B) 24 V type.
  • Page 94 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Bit 0 Digital Output Terminal 27 5-70 Term 32/33 Pulses Per Revolution Bit 1 Digital Output Terminal 29 Range: Function: Bit 2 Digital Output Terminal X 30/6 1024 [1 - 4096 ] Set the encoder pulses per revolution on the Bit 3 Digital Output Terminal X 30/7 motor shaft.
  • Page 95 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 5-97 Pulse Out #X30/6 Bus Control Range: Function: [0 - 100 Set the output frequency transferred to the output terminal X30/6 when the terminal is configured as [45] Bus ctrl. in 5-66 Terminal X30/6 Pulse Output Variable.
  • Page 96: Parameters: 6-** Analog In/Out

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.8.2 6-1* Analog Input 1 3.8 Parameters: 6-** Analog In/Out 3.8.1 6-0* Analog I/O Mode Parameters for configuring the scaling and limits for analog input 1 (terminal 53). The analog inputs can freely be allocated to be either voltage (FC 301: 0..10 V, FC 302: 0..±...
  • Page 97 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 6-14 Terminal 53 Low Ref./Feedb. Value 6-22 Terminal 54 Low Current Range: Function: Range: Function: [-999999.999 - Enter the analog input scaling value that 6-23 reference value, set in 3-02 Minimum Reference. The value must be set at >2 mA 999999.999 ] corresponds to the low voltage/low in order to activate the Live Zero Time-out...
  • Page 98 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.8.4 6-3* Analog Input 3 MCB 101 3.8.5 6-4* Analog Input 4 MCB 101 Parameter group for configuring the scale and limits for Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB analog input 4 (X30/12) placed on option module MCB 101.
  • Page 99 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.8.6 6-5* Analog Output 1 6-53 Terminal 42 Output Bus Control Range: Function: Parameters for configuring the scaling and limits for [0 - 100 %] Holds the level of Output 42 if controlled by analog output 1, i.e.
  • Page 100 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 6-60 Terminal X30/8 Output 6-60 Terminal X30/8 Output Option: Function: Option: Function: I VLT x 100 3-00 Reference Range [-Max - Max] -100% = 0 38.4 x 100 = 175 % mA; 0% = 10 mA; +100% = 20 mA I Motor Norm [102] Feedback...
  • Page 101 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 6-62 Terminal X30/8 Max. Scale 6-70 Terminal X45/1 Output Range: Function: Option: Function: output. Scale the output to give a lower current Example: Inverter norm current (11 kW) = 24 than 20 mA at full scale or 20 mA at an output A.
  • Page 102 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 6-70 Terminal X45/1 Output Current [mA] Option: Function: [137] Speed 4-20 Taken from 3-03 Maximum Reference. 20 mA = Value in 3-03 Maximum Reference. [138] Torque 4-20 Torque reference related to 160% torque. [139] Bus ctrl.
  • Page 103 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 6-82 Terminal X45/3 Output Max Scale Option: Function: [0.00%] 0.00 - Scales the maximum output of the selected 200.00% analog signal on terminal X45/3. Scale the value to the desired maximum value of the current signal output.
  • Page 104: Parameters: 7-** Controllers

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.9 Parameters: 7-** Controllers 7-03 Speed PID Integral Time Range: Function: 3.9.1 7-0* Speed PID Ctrl. Size [1.0 - Enter the speed controller integral time, related 20000 which determines the time the internal PID control takes to correct errors.
  • Page 105 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 7-06 Speed PID Lowpass Filter Time Feedback Range: Function: Disturbed feedback signal signal that varies by a frequency of less than 1.6 Hz. If the feedback signal varies by a higher frequency than 1.6 Hz, the PID regulator does not react.
  • Page 106 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.9.2 7-1* Torque PI Control 7-07 Speed PID Feedback Gear Ratio Range: Function: Parameters for configuring the torque PI control in torque [ 0.0001 - The frequency converter multiplies the open loop (1-00 Configuration Mode). 32.0000 ] speed feedback by this ratio.
  • Page 107 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 7-22 Process CL Feedback 2 Resource 7-34 Process PID Integral Time Option: Function: Range: Function: the source of the second of these 10000 s [0.01 - Enter the PID integral time. The integrator signals.
  • Page 108 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 7-40 Process PID I-part Reset 7-45 Process PID Feed Fwd Resource Option: Function: Option: Function: Yes Select [1] Yes to reset the I-part of the process PID [29] Analog Input X48/2 controller. The selection automatically reverts to [0] [32] Bus PCD Selects a bus reference configured by No.
  • Page 109: Parameters: 8-** Communications And Options

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 7-51 Process PID Feed Fwd Gain 8-02 Control Word Source Range: Function: Option: Function: NOTICE to the reference whereas 7-51 Process PID Feed Fwd Gain has more choices. In winder applications, the This parameter cannot be adjusted feed fwd factor is typically the line speed of the while the motor is running.
  • Page 110 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 8-04 Control Word Timeout Function 8-05 End-of-Timeout Function Option: Function: Select the time-out function. The time-out function activates when the control word fails to be updated within the time [1] Resume Resumes the set-up active before the time-out. period specified in 8-03 Control Word Timeout Time.
  • Page 111 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.10.2 8-1* Ctrl. Word Settings 8-13 Configurable Status Word STW The status word has 16 bits (0-15). Bits 5 and 12-15 are config- urable. Each of these bits can be configured to any of the 8-10 Control Word Profile following options.
  • Page 112 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 8-19 Product Code 8-35 Minimum Response Delay Range: Function: Range: Function: Size related [0 - Select [0] to readout the actual 10 ms [ 1 - 10000 Specify the minimum delay time between 2147483647 ] fieldbus product code according receiving a request and transmitting a...
  • Page 113 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 8-41 Parameters for Signals 8-41 Parameters for Signals Option: Function: Option: Function: 8-43 PCD Read Configu- [1621] Torque [%] High Res. ration. [1622] Torque [%] [1623] Motor Shaft Power [kW] [15] Readout: actual setup [1624] Calibrated Stator Resistance [302] Minimum Reference...
  • Page 114 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 8-41 Parameters for Signals 8-42 PCD Write Configuration Option: Function: Range: Function: [1836] Analog Input X48/2 [mA] Size related [0 - Select the parameters to be assigned to 9999 ] PCD's telegrams. The number of available [1837] Temp.
  • Page 115 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 8-49 BTM Error Log 8-53 Start Select Range: Function: Option: Function: decimal break is the error code (255 Select control of the frequency converter start means no error). function via the terminals (digital input) and/or via the fieldbus.
  • Page 116 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.10.6 8-8* FC Port Diagnostics 8-56 Preset Reference Select Option: Function: These parameters are used for monitoring the Bus [0] Digital Activates Preset Reference selection via a digital communication via the FC Port. input input.
  • Page 117: Parameters: 9-** Profibus

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.11 Parameters: 9-** Profibus For Profibus parameter descriptions, see the Profibus Operating Instructions. 3.12 Parameters: 10-** DeviceNet CAN Fieldbus For Devicenet parameter descriptions, see the Devicenet Operating Instructions. 3.13 Parameters: 12-** Ethernet For Ethernet parameter descriptions, see the Ethernet Operating Instructions.
  • Page 118: Parameters: 13-** Smart Logic Control

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.14 Parameters: 13-** Smart Logic Control Start event P13-01 State 1 Event 1/ 3.14.1 Prog. Features Action 1 State 2 Event 2/ Stop Action 2 event P13-02 Smart Logic Control (SLC) is essentially a sequence of user- Stop event P13-02 defined actions (see 13-52 SL Controller Action [x]) executed...
  • Page 119 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-01 Start Event 13-01 Start Event Select the boolean (TRUE or FALSE) input to activate Smart Logic Select the boolean (TRUE or FALSE) input to activate Smart Logic Control. Control. Option: Function: Option: Function: Torque limit...
  • Page 120 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-01 Start Event 13-02 Stop Event Select the boolean (TRUE or FALSE) input to activate Smart Logic Select the boolean (TRUE or FALSE) input to deactivate Smart Control. Logic Control. Option: Function: Option: Function: [101] RS Flipflop 7...
  • Page 121 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Operand. Comparators are evaluated once in each scan 13-02 Stop Event interval. Use the result (TRUE or FALSE) directly. All Select the boolean (TRUE or FALSE) input to deactivate Smart parameters in this parameter group are array parameters Logic Control.
  • Page 122 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-10 Comparator Operand 13-10 Comparator Operand Array [6] Array [6] Option: Function: Option: Function: [30] Counter A Number of counts. [76] Below feedback The feedback is below the limit set in 4-56 Warning Feedback Low. [31] Counter B Number of counts.
  • Page 123 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-10 Comparator Operand 13-11 Comparator Operator Array [6] Array [6] Option: Function: Option: Function: [130] Digital input DI18 Digital input 18. High = True. Select the operator to be used in the comparison.
  • Page 124 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 2 parameters are used and the output can be used in the 13-15 RS-FF Operand S logic rules and as events. Option: Function: On reference Torque limit Current Limit Out of current range Below I low Flip Flop Output Above I high...
  • Page 125 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-15 RS-FF Operand S 13-16 RS-FF Operand R Option: Function: Option: Function: [73] SL Time-out 6 [24] Comparator 2 [74] SL Time-out 7 [25] Comparator 3 [75] Start command given [26] Logic rule 0 [76] Digital input x30/2 [27]...
  • Page 126 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide combined with the settings of 13-43 Logic Rule Operator 2 13-16 RS-FF Operand R and 13-44 Logic Rule Boolean 3, yielding the final result Option: Function: (TRUE/FALSE) of the logic rule. [97] RS Flipflop 3 13-40 Logic Rule Boolean 1 [98]...
  • Page 127 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-40 Logic Rule Boolean 1 13-40 Logic Rule Boolean 1 Array [6] Array [6] Option: Function: Option: Function: [43] Ok key [97] RS Flipflop 3 See 13-1* Comparators [44] Reset key [98] RS Flipflop 4 See 13-1* Comparators [45]...
  • Page 128 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-42 Logic Rule Boolean 2 13-42 Logic Rule Boolean 2 Array [6] Array [6] Option: Function: Option: Function: Below I low [76] Digital input x30/2 Above I high [77] Digital input x30/3 [10] Out of speed range [78]...
  • Page 129 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-43 Logic Rule Operator 2 13-44 Logic Rule Boolean 3 Array [6] Array [6] Option: Function: Option: Function: Select the second logical operator to be used [20] Alarm (trip) on the boolean input calculated in [21] Alarm (trip lock) 13-40 Logic Rule Boolean 1, 13-41 Logic Rule...
  • Page 130 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-44 Logic Rule Boolean 3 13-51 SL Controller Event Array [6] Array [20] Option: Function: Option: Function: or [21] Advanced ETR. If the alarm Below I low 164 ATEX ETR cur.lim.alarm is Above I high active, the output is 1.
  • Page 131 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-51 SL Controller Event 13-52 SL Controller Action Array [20] Array [20] Option: Function: Option: Function: [76] Digital input x30/2 following actions are available for selection: [77] Digital input x30/3 [78] Digital input x30/4 [0] *DISABLED [79] Digital input x46/1...
  • Page 132 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 13-52 SL Controller Action 13-52 SL Controller Action Array [20] Array [20] Option: Function: Option: Function: [15] Select preset ref Selects preset reference 5. [35] Set digital out D Any output with SL output D is low. If the active preset reference is changed, it merges with other preset reference [36] Set digital out E...
  • Page 133: Parameters: 14-** Special Functions

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide NOTICE 3.15 Parameters: 14-** Special Functions To avoid a trip, the frequency converter can adapt 3.15.1 14-0* Inverter Switching the switching frequency automatically. 14-03 Overmodulation 14-00 Switching Pattern Option: Function: Option: Function: Off Select [0] Off for no overmodulation of the output Select the switching pattern: 60°...
  • Page 134 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 14-10 Mains Failure 14-10 Mains Failure Note: Note: Options [1], [2], [5], [7] are not active when the option [2] Torque Options [1], [2], [5], [7] are not active when the option [2] Torque is selected in parameter 1-00 Configuration Mode.
  • Page 135 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 14-10 Mains Failure 14-10 Mains Failure Note: Note: Options [1], [2], [5], [7] are not active when the option [2] Torque Options [1], [2], [5], [7] are not active when the option [2] Torque is selected in parameter 1-00 Configuration Mode.
  • Page 136 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 14-10 Mains Failure 14-11 Mains Voltage at Mains Fault Range: Function: Note: NOTICE Options [1], [2], [5], [7] are not active when the option [2] Torque is selected in parameter 1-00 Configuration Mode. Note for converting between VLT 5000 Option: Function:...
  • Page 137 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide NOTICE 3.15.4 14-2* Trip Reset Remember to set switches S201 (A53) and S202 (A54) as Parameters for configuring auto reset handling, special trip specified below when performing a control card test in handling and control card self test or initialisation.
  • Page 138 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 14-22 Operation Mode 14-25 Trip Delay at Torque Limit Option: Function: Range: Function: 60 s [0 - Enter the torque limit trip delay in seconds. When 33 20 60 s] the output torque reaches the torque limits FC 302 (4-16 Torque Limit Motor Mode and 4-17 Torque Limit Generator Mode), a warning is triggered.
  • Page 139 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide function along with an external electro-mechanical brake 14-40 VT Level attached to the application. Range: Function: 14-30 Current Lim Ctrl, Proportional Gain Enter the level of motor magnetisation at low speed. Selection of a low value reduces energy Range: Function: loss in the motor, but also reduces load...
  • Page 140 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.15.7 14-5* Environment 14-52 Fan Control Select minimum speed of the main fan. These parameters help the frequency converter to operate Option: Function: under special environmental conditions. Fan runs at low speed below 35 °C, and at full 14-50 RFI Filter speed at approx.
  • Page 141 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.15.8 14-7* Compatibility 14-55 Output Filter Option: Function: The parameters in this group are for setting of compati- frequencies. Operation is possible with all control bility for VLT 3000, VLT 5000 to FC 300. principles.
  • Page 142 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 14-90 Fault Level 14-90 Fault Level Use this parameter to customise fault levels. Use this parameter to customise fault levels. Option: Function: Option: Function: [0] Off Use [0] Off with caution as it ignores all Warnings [2] Trip &...
  • Page 143: Parameters: 15-** Drive Information

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.16 Parameters: 15-** Drive Information 15-07 Reset Running Hours Counter Option: Function: 3.16.1 15-0* Operating Data Do not reset Reset Select [1] Reset and press [OK] to reset the 15-00 Operating hours counter Running Hours counter to zero (see Range:...
  • Page 144 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 15-10 Logging Source 15-12 Trigger Event Array [4] Select the trigger event. When the trigger event occurs, a window is applied to freeze the log. The log then retains a Option: Function: specified percentage of samples before the occurrence of the [1657] Feedback [RPM] trigger event (15-14 Samples Before Trigger).
  • Page 145 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide Status word 15-22 Historic Log: Time Control word Array [50] Range: Function: Extended status word 0 ms [0 - View the time at which the logged event Events are logged with value, and time stamp in ms. The 2147483647 occurred.
  • Page 146 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 15-41 Power Section 15-53 Power Card Serial Number Range: Function: Range: Function: [0 - 0 ] View the FC type. The read-out is identical to the [0 - 0 ] View the power card serial number. FC 300 Series power field of the type code 15-58 Smart Setup Filename definition, characters 7-10.
  • Page 147 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 15-71 Slot A Option SW Version 15-89 Configuration Change Counter Range: Function: Range: Function: NOTICE [0 - 0 ] View the software version for the option installed [0 - 65535 ] in slot A. This parameter cannot be adjusted while the motor is running.
  • Page 148: Parameters: 16-** Data Read-Outs

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.17.1 16-1* Motor Status 3.17 Parameters: 16-** Data Read-outs 16-10 Power [kW] 16-00 Control Word Range: Function: Range: Function: 0 kW [0 - Displays motor power in kW. The value shown [0 - 65535 ] View the Control word sent from the 10000 is calculated based on the actual motor frequency converter via the serial communi-...
  • Page 149 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.17.2 16-24 Calibrated Stator Resistance 16-16 Torque [Nm] Range: Function: 16-24 Calibrated Stator Resistance the rated torque. Some motors supply more than 160% torque. Consequently, the min. Range: Function: value and the max. value depend on the max. 0.0000 Ohm [0.0000 - 100.0000 Displays the Calibrated...
  • Page 150 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.17.4 16-47 Motor Phase W Current 16-36 Inv. Nom. Current Range: Function: 16-47 Motor Phase W Current Size related [0.01 - View the inverter nominal current, Range: Function: 10000 A] which must match the nameplate data on the connected motor.
  • Page 151 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 16-53 Digi Pot Reference 16-61 Terminal 53 Switch Setting Range: Function: Option: Function: [-200 - 200 ] View the contribution of the Digital Potenti- View the setting of input terminal 53. ometer to the actual reference. Current Voltage 16-57 Feedback [RPM]...
  • Page 152 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 16-71 Relay Output [bin] 16-77 Analog Out X30/8 [mA] Range: Function: Range: Function: [0 - 511 ] View the settings of all relays. [0 - 30 ] View the actual value at input X30/8 in mA. 16-78 Analog Out X45/1 [mA] Range: Function:...
  • Page 153 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 16-86 FC Port REF 1 Range: Function: [-200 - View the two-byte status word (STW) sent to the 200 ] Bus-Master. Interpretation of the status word depends on the fieldbus option installed and the control word profile selected in 8-10 Control Profile.
  • Page 154: Parameters: 17-** Motor Feedb. Option

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.18 Parameters: 17-** Motor Feedb. 17-21 Resolution (Positions/Rev) Option Range: Function: Size related [ 4 - Select the resolution of the absolute 131072 ] encoder, i.e. the number of counts Additional parameters to configure the Encoder (MCB 102) per revolution.
  • Page 155 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.18.4 17-6* Monitoring and Application 17-50 Poles Range: Function: This parameter group is for selecting additional functions [2 - 8 ] Set the number of poles on the resolver. when Encoder option MCB 102 or Resolver Option MCB The value is stated in the data sheet for resolvers.
  • Page 156: Parameters: 18-** Data Readouts 2

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.19 Parameters: 18-** Data Readouts 2 18-36 Analog Input X48/2 [mA] Range: Function: [-20 - 20 ] View the actual current measured at input X48/2. 18-37 Temp. Input X48/4 Range: Function: [-500 - View the actual temperature measured at input 500 ] X48/4.
  • Page 157: Parameters: 30-** Special Features

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.20 Parameters: 30-** Special Features 30-00 Wobble Mode Option: Function: Rel. Freq., 3.20.1 30-0* Wobble Function Abs. Time Rel. Freq., The wobble function is primarily used for synthetic yarn Up/ Down winding applications. The wobble option is to be installed Time in the frequency converter controlling the traverse drive.
  • Page 158 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 30-04 Wobble Jump Frequency [Hz] 30-19 Wobble Delta Freq. Scaled Range: Function: Range: Function: system has a very high inertia a high jump 0 Hz [0 - 1000 Hz] Readout parameter. View the actual frequency may create a torque limit warning or wobble delta frequency after scaling has trip (warning/alarm 12) or an overvoltage warning...
  • Page 159 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 30-81 Brake Resistor (ohm) Range: Function: parameter is only active in frequency converters with an integral dynamic brake. 30-83 Speed PID Proportional Gain Range: Function: Size related [0 - Enter the speed controller proportional gain.
  • Page 160: Parameters: 35-** Sensor Input Option

    Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 3.21 Parameters: 35-** Sensor Input Option 35-06 Temperature Sensor Alarm Function Select the alarm function: Option: Function: 3.21.1 35-0* Temp. Input Mode (MCB 114) Stop Stop and trip 35-00 Term. X48/4 Temperature Unit Select the unit to be used with temperature input X48/4 settings 3.21.2 35-1* Temp.
  • Page 161 Parameter Descriptions ® AutomationDrive FC 301/302 Programming Guide 35-25 Term. X48/7 Temp. Monitor 35-37 Term. X48/10 High Temp. Limit Range: Function: This parameter gives the possibility of enabling or disabling the temperature monitor for terminal X48/7. The temperature limits Size related [ par.
  • Page 162: Parameter Lists

    Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4 Parameter Lists 4.1 Parameter Lists 4.1.1 Introduction Frequency converter series All = valid for FC 301 and FC 302 series 01 = valid for FC 301 only 02 = valid for FC 302 only Changes during operation ”TRUE”...
  • Page 163: Conversion

    Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4.1.2 Conversion Conversion index Conversion factor The various attributes of each parameter are displayed in factory setting. Parameter values are transferred as whole numbers only. Conversion factors are therefore used to transfer decimals. 1000000 100000 4-12 Motor Speed Low Limit [Hz] has a conversion factor of...
  • Page 164 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 1-10 Motor Construction AC motor PM Non salient Motor Flux w/ Flux w/ 1-01 Motor Control Flux Flux plus motor plus motor Principle mode sensorless mode sensorless feedback feedback 1-22 Motor Voltage 1-23 Motor Frequency 1-24 Motor Current 1-25 Motor Nominal Speed...
  • Page 165 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 1-10 Motor Construction AC motor PM Non salient Motor Flux w/ Flux w/ 1-01 Motor Control Flux Flux plus motor plus motor Principle mode sensorless mode sensorless feedback feedback 1-68 Minimum Inertia 1-69 Maximum Inertia 1-71 Start Delay 1-72 Start Function...
  • Page 166 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 1-10 Motor Construction AC motor PM Non salient Motor Flux w/ Flux w/ 1-01 Motor Control Flux Flux plus motor plus motor Principle mode sensorless mode sensorless feedback feedback 2-19 Over-voltage Gain 2-20 Release Brake Current 2-21 Activate Brake Speed [RPM]...
  • Page 167 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 1-10 Motor Construction AC motor PM Non salient Motor Flux w/ Flux w/ 1-01 Motor Control Flux Flux plus motor plus motor Principle mode sensorless mode sensorless feedback feedback 4-39 Tracking Error After Ramping Timeout 4-50 Warning Current Low 4-51 Warning Current High...
  • Page 168 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 1-10 Motor Construction AC motor PM Non salient Motor Flux w/ Flux w/ 1-01 Motor Control Flux Flux plus motor plus motor Principle mode sensorless mode sensorless feedback feedback 7-33 Process PID Proportional Gain 7-34 Process PID Integral Time 7-35 Process PID Differen-...
  • Page 169 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 1-10 Motor Construction AC motor PM Non salient Motor Flux w/ Flux w/ 1-01 Motor Control Flux Flux plus motor plus motor Principle mode sensorless mode sensorless feedback feedback [3] Coasting [4] Kinetic back-up [5] Kinetic back-up, trip [6] Alarm 14-11 Mains Voltage at Mains...
  • Page 170 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 2) Variable torque 3) AEO 4) Constant power 5) Used in flystart 6) Used when 1-03 Torque Characteristics is constant power 7) Not used when 1-03 Torque Characteristics = VT 8) Part of resonance damping 9) Not AC brake 10) Torque open loop 11) Torque...
  • Page 171 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4.1.4 0-** Operation/Display Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 0-0* Basic Settings 0-01 Language [0] English 1 set-up TRUE Uint8 0-02 Motor Speed Unit [0] RPM...
  • Page 172 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4.1.5 1-** Load/Motor Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion operation index 1-0* General Settings 1-00 Configuration Mode ExpressionLimit All set-ups TRUE Uint8 1-01 Motor Control Principle ExpressionLimit...
  • Page 173 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion operation index Min Speed Normal Magnetising 1-52 [Hz] ExpressionLimit All set-ups TRUE Uint16 1-53 Model Shift Frequency ExpressionLimit All set-ups FALSE...
  • Page 174 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4.1.6 2-** Brakes Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion operation index 2-0* DC-Brake 2-00 DC Hold Current 50 % All set-ups TRUE Uint8 2-01 DC Brake Current...
  • Page 175 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion operation index 3-10 Preset Reference All set-ups TRUE Int16 3-11 Jog Speed [Hz] ExpressionLimit All set-ups TRUE Uint16 3-12...
  • Page 176 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion operation index 3-76 Ramp 4 S-ramp Ratio at Accel. End 50 % All set-ups TRUE Uint8 Ramp 4 S-ramp Ratio at Decel.
  • Page 177 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion operation index 4-50 Warning Current Low All set-ups TRUE Uint32 4-51 Warning Current High ImaxVLT (P1637) All set-ups TRUE Uint32...
  • Page 178 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 5-41 On Delay, Relay 0.01 s All set-ups TRUE Uint16 5-42 Off Delay, Relay 0.01 s All set-ups TRUE...
  • Page 179 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 6-13 Terminal 53 High Current 20 mA All set-ups TRUE Int16 Terminal 53 Low Ref./Feedb. 0 ReferenceFeed- 6-14 Value...
  • Page 180 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 6-71 Terminal X45/1 Min. Scale All set-ups TRUE Int16 6-72 Terminal X45/1 Max. Scale 100 % All set-ups TRUE...
  • Page 181 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation Process PID Gain Scale at Min. 7-43 Ref. 100 % All set-ups TRUE Int16 Process PID Gain Scale at Max.
  • Page 182 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 8-42 PCD Write Configuration ExpressionLimit 2 set-ups TRUE Uint16 8-43 PCD Read Configuration ExpressionLimit 2 set-ups TRUE Uint16...
  • Page 183 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 9-68 Status Word 1 0 N/A All set-ups TRUE 9-70 Edit Set-up [1] Set-up 1 All set-ups TRUE Uint8 9-71 Profibus Save Data Values [0] Off All set-ups TRUE Uint8 9-72 ProfibusDriveReset [0] No action 1 set-up FALSE...
  • Page 184 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4.1.15 12-** Ethernet Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 12-0* IP Settings 12-00 IP Address Assignment ExpressionLimit 2 set-ups TRUE Uint8 12-01 IP Address...
  • Page 185 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 12-68 Cumulative Counters 0 N/A All set-ups TRUE Uint32 12-69 Ethernet PowerLink Status 0 N/A All set-ups TRUE Uint32...
  • Page 186 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4.1.17 14-** Special Functions Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 14-0* Inverter Switching 14-00 Switching Pattern ExpressionLimit All set-ups TRUE Uint8 14-01 Switching Frequency ExpressionLimit...
  • Page 187 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 14-80 Option Supplied by External 24VDC [1] Yes 2 set-ups FALSE Uint8 14-88 Option Data Storage 0 N/A 2 set-ups TRUE Uint16 14-89 Option Detection [0] Protect Option Config. 1 set-up TRUE Uint8 14-9* Fault Settings 14-90 Fault Level...
  • Page 188 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 15-61 Option SW Version 0 N/A All set-ups FALSE VisStr[20] 15-62 Option Ordering No 0 N/A All set-ups FALSE...
  • Page 189 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 16-30 DC Link Voltage All set-ups FALSE Uint16 16-32 Brake Energy /s 0 kW All set-ups FALSE Uint32 16-33 Brake Energy /2 min 0 kW All set-ups FALSE Uint32 16-34 Heatsink Temp. 0 °C All set-ups FALSE...
  • Page 190 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 16-92 Warning Word 0 N/A All set-ups FALSE Uint32 16-93 Warning Word 2 0 N/A All set-ups FALSE Uint32 16-94 Ext. Status Word 0 N/A All set-ups FALSE Uint32 4.1.20 17-** Motor Feedb.Option Par.
  • Page 191 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide 4.1.22 30-** Special Features Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 30-0* Wobbler [0] Abs. Freq., Abs. 30-00 Wobble Mode Time All set-ups FALSE Uint8...
  • Page 192 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation Absolute Encoder Cable 32-08 Length 2 set-ups TRUE Uint16 32-09 Encoder Monitoring [0] Off 2 set-ups TRUE Uint8...
  • Page 193 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 32-8* Velocity & Accel. 32-80 Maximum Velocity (Encoder) 1500 RPM 2 set-ups TRUE Uint32 32-81 Shortest Ramp 2 set-ups...
  • Page 194 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 33-28 Marker Filter Configuration [0] Marker filter 1 2 set-ups TRUE Uint8 33-29 Filter Time for Marker Filter 0 ms 2 set-ups TRUE...
  • Page 195 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 33-87 Terminal state at alarm [0] Do nothing 2 set-ups TRUE Uint8 33-88 Status word at alarm 0 N/A 2 set-ups TRUE...
  • Page 196 Parameter Lists ® AutomationDrive FC 301/302 Programming Guide Par. No. # Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 34-60 Synchronizing Status 0 N/A All set-ups TRUE Int32 34-61 Axis Status 0 N/A All set-ups TRUE Int32...
  • Page 197: Troubleshooting

    Troubleshooting ® AutomationDrive FC 301/302 Programming Guide 5 Troubleshooting If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked 5.1 Status Messages (see also Table 5.1). 5.1.1 Warnings/Alarm Messages Alarms that are trip-locked offer additional protection, meaning that the mains supply must be switched off A warning or an alarm is signalled by the relevant LED on...
  • Page 198 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference Hardware mismatch Short Circuit Control word time-out 8-04 Control Word Timeout Function Temp. Input Error Param Error Hoist Mech. Brake Parameter group 2-2* Internal Fans External Fans Brake resistor short-circuited Brake resistor power limit 2-13 Brake Power...
  • Page 199 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference Feedback Error 4-30 Motor Feedback Loss Function Output Frequency at Maximum Limit Mechanical Brake Low 2-20 Release Brake Current Voltage Limit Control Board Over-temperature Heat sink Temperature Low Option Configuration has Changed Safe Stop 5-19 Terminal 37 Safe...
  • Page 200 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference Progr. Memory Reset by CPU User abort No more SDO channels HW end limit Too many inter. No ext. 24 V GOSUB > limit Return @ limit D.out overload LINK failed Illegal double arg.
  • Page 201 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide Bit Hex Alarm Word Alarm Word 2 Warning Warning Extended Extended Word Word 2 Status Word Status Word 00000010 Ctrl. Word TO ServiceTrip, Ctrl. Word TO Catch Up Profibus OFF3 (A17) (reserved) (W17) catch up command active active, e.g.
  • Page 202 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide Bit Hex Alarm Word Alarm Word 2 Warning Warning Extended Extended Word Word 2 Status Word Status Word 24 01000000 16777216 Mains Failure reserved Mains Failure reserved Unused Drive Bypass (A36) (W36) 25 02000000 33554432 1.8V Supply Current Limit...
  • Page 203 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide Activate the functions in 2-10 Brake Function Running AMA in 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the Increase 14-26 Trip Delay at Inverter Fault motor more accurately and reduces thermal If the alarm/warning occurs during a power sag, loading.
  • Page 204 Troubleshooting Record the value of the following parameters and contact Check for proper fan operation. your Danfoss supplier: Cycle power to the frequency converter and 15-40 FC Type check that the fan operates briefly at start-up.
  • Page 205 The trip and reset points are different based on the Check for loose or missing wiring frequency converter power size. It may be necessary to contact your Danfoss supplier or Troubleshooting service department. Note the code number for further Check for the following conditions.
  • Page 206 Check for a defective control card. control board hardware Check for a defective option card. 5376-6231 Internal fault. Contact your Danfoss supplier or Danfoss Service Department. If a 24 V DC power supply is used, verify proper supply power. Table 5.4 Internal Fault Codes WARNING 47, 24 V supply low The 24 V DC is measured on the control card.
  • Page 207 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide WARNING 59, Current limit ALARM 68, Safe Stop activated The current is higher than the value in 4-18 Current Limit. Safe Torque Off has been activated. To resume normal Ensure that Motor data in parameters 1-20 to 1-25 are set operation, apply 24 V DC to terminal 37, then send a reset correctly.
  • Page 208 Troubleshooting ® AutomationDrive FC 301/302 Programming Guide the frequency converter is set to run with fewer inverters, WARNING/ALARM 104, Mixing fan fault and remains on. The fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is ALARM 78, Tracking error turned on.
  • Page 209: Index

    ® Index AutomationDrive FC 301/302 Programming Guide Index Copy/Save, 0-5*................... 32 Ctrl. Word Settings, 8-1*..............109 Current Limit Control, 14-3*..............137 Abs. Enc. Interface, 17-2*............... 152 rating....................201 Adjustable Warnings, 4-5*.............. 73 Adv. Motor Data, 1-3*................39 Data Start Adjust, 30-2*................. 156 Log Settings..................
  • Page 210 ® Index AutomationDrive FC 301/302 Programming Guide Motor current....................204 data................... 201, 205 Historic Log, 15-2*................142 Data, 1-2*.................... 37 Feedb. Option, 17-**..............152 Feedback Monitoring, 4-3*............71 Limits, 4-1*..................70 I/O Options, 5-8*.................. 92 power....................204 protection................... 48 Inc. Enc. Interface, 17-1*..............152 Status....................
  • Page 211 ® Index AutomationDrive FC 301/302 Programming Guide Synchronous motor speed..............3 Ramp 2, 3-5*....................64 Temp. 3, 3-6*....................65 Input Mode (MCB 114), 35-0*............ 158 4, 3-7*....................66 Input X48/10 (MCB 114), 35-3*..........159 Ramps, 3-4* Ramp 1................63 Input X48/4 (MCB 114), 35-1*............ 158 Input X48/7 (MCB 114), 35-2*............
  • Page 212 130R0334 MG33MH02 Rev. 2013-09-30 *MG33MH02*...

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents