HM700A1000 Electrode Steam Humidifier
ELECTRICAL
High Voltage Wiring
Requirements
• Humidifier MUST be connected GFCI circuit.
• 15 amp, 120/240 volt circuit required.
• Local disconnect must be installed for future servicing.
• Wiring must be performed by a licensed electrician.
High Voltage Wiring Install Process
Hard wire the unit to local circuit disconnect as shown below.
1. Connect ground to the peg at right.
1
2
3
4
5
M36307
2. Connect neutral to terminal 1 (or hot, in
the case of 240 volt).
1
2
3
4
5
M36308
3. Connect hot to terminal 5.
1
2
3
4
5
M36309
4. Insert jumper wire:
120 Volt: use the yellow jumper wire (supplied)
to connect terminals 1 & 4.
1
2
3
4
5
M36310
120 Volt: use the yellow jumper wire (supplied)
to connect terminals 1 & 2.
1
2
3
4
5
M36311
33-00162EFS—03
5. Remove the ground wire screw from the case body.
M36312
6. Clip the other end of the green ground wire as close as possible to the drain
valve. Remove the cut wire.
M36313
2