2. Select "COM3" in the "Port" drop-down list.
3. Set the "BaudRate", "DataBits", "StopBits" and "ParityBits" in the "Settings" option
box.
4. Other parameters remain the default, click "Submit".
Step 4 Configure the working mode of the Modbus gateway.
1. Log in to the Web configuration interface and select " Main Menu > Modbus
Settings > SlaveID ".
2. In the "Channel NO." is 3, click the "channel Type" drop-down list box and select
"ASCII Master".
3. Click "Add" and enter "192.168.1.80" in the "Remote IP Address" text box.
4. Enter "503" in the "TCP port" text box.
5. Enter "3" in the "Slave ID Start" and "Slave ID End" text boxes.
6. Enter "0" in the "Slave ID Offset" text box.
7. Click "OK".
8. Save the configuration, click "Submit".