Setting With Engineering Tool 2 - Toshiba V Series Operation Manual

Integrated controller, ethernet module / ds connection module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Chapter 3 Setting
3
3.2.5

Setting with Engineering Tool 2

34
Network Parameter Setting
The network parameters include IP address, subnet mask and multicast address.
Registered parameters can be downloaded into the Ethernet modules as described
below.
Preparations on the Ethernet module side
Connect the Engineering tool to the serial communication port (TOOL) of the Ethernet
module with the RS-232C cable.
Then, make a setting for verifying the transmission parameter setting screen from the
serial communication port (TOOL).
Start the configuration editor [Hardware configuration] for controller A to open the screen
showing the registered hardware configuration of controller A. Select EN741 and
execute [Edit (E)] [Parameter setting (P)] to open the screen below. When [Tool and
Ether card (B)] is clicked, the network information that the Ethernet module has can be
displayed from the serial communication port.
Network Parameter Verification
Set the network to which EN7 modules are connected.
(1) Start engineering tool 2 and register an EN7 module from product tree. Select [New
(W)] with selecting the station under the registered system. For system registration,
refer to the Engineering Tool 2 operation manual.
model 3000 Ethernet Module / DS Connection Module Operation Manual