Samsung MXD-K100XN Installation Manual page 19

Air handling unit application kit
Table of Contents

Advertisement

Sensor installation example 1
1) Check the sensor and the sensor holder.
NOTE
Type
Sensor OD(mm)
EVA IN sensor
Ø 6
EVA OUT sensor
Ø 7
2) Braze the sensor holder on the selected location of the pipe.
Sensor attachment method.
NOTE
• Choose the location where temperature can be measured
correctly. (Refer to page 18)
• Try to attach closely to the contact surface before brazing.
• Distinguish EVA IN/OUT sensor and attach it. (EVA IN/OUT sensor
size is different.)
3) Insert sensor and the sensor clip in the sensor holder.
4) Bend end of the sensor clip to fix the sensor.
5) Attach the insulator around the sensor.
Sensor holder ID (mm)
Ø 6.8
Ø 7.8
Sensor clip
Sensor holder
Insulator
Sensor
Pipe
Sensor holder
Sensor clip
Insulator
Sensor
English
19

Hide quick links:

Advertisement

Table of Contents
loading