Technical data

6.1

Technical specifications of the CP 1243-1

Table 6- 1
Technical specifications of the CP 1243-1
Technical specifications
Article number
Attachment to Industrial Ethernet
Quantity
Design
Properties
Transmission speed
Permitted cable lengths (Ethernet)
0 ... 55 m
0 ... 85 m
0 ... 100 m
Electrical data
Power supply
Current consumption (typical)
Effective power loss (typical)
Permitted ambient conditions
Ambient temperature
Relative humidity
Design, dimensions and weight
Module format
Degree of protection
Weight
CP 1243-1
Operating Instructions, 12/2016, C79000-G8976-C365-02
6GK7 243-1BX30-0XE0
1
RJ-45 jack
100BASE-TX, IEEE 802.3-2005, half duplex/full duplex, autocrossover, autonego-
tiation, galvanically isolated
10/100 Mbps
(Alternative combinations per length range) *
Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
Max. 85 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable with
IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable +
10 m TP Cord via IE FC RJ45 Outlet
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
From the S7-1200 backplane bus
From the S7-1200 backplane bus
From the S7-1200 backplane bus
During operation with the rack in-
stalled horizontally
During operation with the rack in-
stalled vertically
During storage
During transportation
During operation
Compact module for S7-1200, single width
IP20
122 g
5 VDC
250 mA
1.25 W
-20 °C to +70 °C
-20 °C to +60 °C
-40 ℃ to +70 ℃
-40 ℃ to +70 ℃
≤ 95 % at 25 °C, no condensation