Mounting
4.2 Mounting the enclosure
4.2
Mounting the enclosure
The enclosure is intended for wall mounting and should be secured with the wall supports
supplied with it. Use the following template for the drilling.
B = 950 mm for 6DL2804-xxDxx
Figure 4-1
NOTICE
Reduction of the degree of protection
If the device is not installed horizontally, this may lead to a reduction in the degree of
protection. Furthermore, the operating ambient temperature is 30°C lower with vertical
installation than with horizontal installation. The temperature information on the type plate
always applies to horizontal installation. Therefore, always install the device horizontal, in
such a way that the cable entries face downward.
NOTICE
• Remember the maximum thermal load on the cables and wiring. The degree of
• Note that it is only permitted to connect and disconnect the cables to the power supply
16
Drilling template for securing the device
protection is only ensured when suitable cables and wires are used and correctly
installed.
module if the module has been powered down.
B = 650 mm for 6DL2804-xxExx
Wall-mount enclosure 6DL2804-0xxxx
Hardware Installation Manual, 08/2009, A5E00378691N-02