Alarms - flowair T-box User Manual

Hide thumbs Also See for T-box:
Table of Contents

Advertisement

Alarms

Alarms
warnings
• Gas sensor: level 1
signal from gas detector, level I
• Gas sensor: level 2
signal from gas detector, level II
• Antifreeze heat recover exchanger ON
antifreeze mode of heat recovery
exchanger is on
• Filter work time
check lters contamination level
• Filter presure
dirty lter of KM, change the lter, if
pressure switch is not applied make
a bridge (jumper) between PRDN IN
and GND
www. owair.com
Alarms
alarms
• Real time clock error
set the T-box time again
• Temperature sensor T1/T2/T3/T4/T5
check temperature sensor
• Roof fan fuse
check fuse of roof fan in DRV module
• Roof fan TK
thermal protection alarm of roof fan
• Fan 3V fuse
check fuse of fan of LEO heater in
DRV module
• Fan EC fuse
check fuse of fan of LEO M heater in
DRV module
• Fan EC not connected
check connection of fan of LEO M
heater
List of alarms
• Antifreeze water exchanger ON
antifreeze mode of water heat
exchanger is on
• DRV group error
Addressing failure. Check binary
address set in DRV and use search
button again
• Connection error
no communication between DRV and
T-box, check connection and DRV
power supply
• DUO heater not connected
no communication between DRV of
fan heater part of ELiS DUO, check
connection between DRV of air curtain
part and DRV of fan heater part
103

Advertisement

Table of Contents
loading

Table of Contents