Troubleshooting/Faq; Firmware Update Via Wbm Or Cli Not Possible - Siemens SCALANCE W1780 Configuration Manual

Industrial wireless lan
Table of Contents

Advertisement

Troubleshooting/FAQ

8.1

Firmware update via WBM or CLI not possible

Cause
If there is a power failure during the firmware update, it is possible that the device is no longer
accessible using Web Based Management or the CLI.
When pressing the button, make sure you adhere to the instructions in the section "Reset
button".
Solution
You can then also assign firmware to a SCALANCE W using TFTP.
Follow the steps below to load new firmware using TFTP:
1. Turn off the power to the device.
2. Now press the Reset button and reconnect the power to the device while holding down the
button.
3. Hold down the button until the red fault LED (F) starts to flash after approximately 2 seconds.
4. Now release the button. The bootloader waits in this state for a new firmware file that you
can download by TFTP.
5. Connect a PC to the SCALANCE W over the Ethernet interface.
6. Assign an IP address to the SCALANCE W with the Primary Setup Tool.
7. Open a DOS box and change to the directory where the file with the new firmware is located
and then execute the command "tftp -i <ip address> PUT <firmware>". As an alternative,
you can use a different TFTP client.
8. Close the cover to ensure that the device is closed and water and dust proof.
Note
Use of CLI and TFTP in Windows 7
If you want to access the CLI or TFTP in Windows 7, make sure that the relevant functions are
enabled in Windows 7.
SCALANCE W1780/W1740 according to IEEE 802.11ac Web Based Management
Configuration Manual, 11/2019, C79000-G8976-C485-03
8
339

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scalance w1740Scalance w1780 seriesScalance w1740 seriesScalance w1788-2 m12 eecScalance w1788-1 m12Scalance w1788-2 m12 ... Show all

Table of Contents