Honeywell apex Step-By-Step page 2

Single 4-wire smoke zone with sounders
Hide thumbs Also See for apex:

Advertisement

Step-by-Step
- Multiple 4-Wire Smoke Zones with Sounders -
Objective
To activate the sounders on
all smokes after any smoke
detector is activated
Sequence of Operation
When the panel detects an alarm from any fire zone, the panel will activate the on board relay to activate the trigger
wire (purple see wiring diagram below) which in turn with sound ALL sounders.
To Reset:
1. Press Code 1 time
2. Press Code + 6 (Smoke Power Reset)
3. Arm and Disarm the panel (to Clear the Alarm Memory)
Required Programming
Location
9940
9940
4097
4119
0185
4055
Multiple 4-wire smoke zones using the RRS-MOD with No EOL Supervision Relay
Apex Destiny 6100 Control Panel, rev. 8.05 or greater
System Sensor Smokes: 4WTA-B, 4WTAR-B, 4WITAR-B
System Sensor RRS-MOD
Value
Function
01 (zone #)
Zone Type = 006
Zone Options 1 = 080
Zone Options 2 = 001
Device Type = 000 (onboard zones) or 001 (Zone Expander HWB416)
Enter the 2 digit input #
02 (zone #)
Zone Type = 006
Zone Options 1 = 080
Zone Options 2 = 001
Device Type = 000 (onboard zones) or 001 (Zone Expander HWB416)
Enter the 2 digit input #
001
Enable Control Channel 1
008
Assign Control Channel 1 to the on-board relay
001
Assign the "fire" Trigger
006
002 (on – on any fire alarm) + 004 (off – restore action for fire alarm is
disarming the control) = 006
Equipment List
- 2 -
Tech Support
Updated 11/2/07