Suitable lightning protectors are available in the range of accessories of SIMATIC
NET Industrial WLAN:
● Lightning protector LP798-1N (order no. 6GK5798-2LP00-2AA6)
● Lightning protector LP798-2N (order no. 6GK5798-2LP10-2AA6)
Note
We recommend that you use the maintenance-free lightning protector LP798-2N.
Exception:
When there is also DC power is supplied via the antenna cable. In this case, only
the lightning protector LP798-1N can be used.
WARNING
Danger due to lightning strikes
Installing this lightning protector between an antenna and a SCALANCE W700
is not adequate protection against a lightning strike. The lightning protectors
listed above only work within the framework of a comprehensive lightning
protection concept. If you have questions, ask a qualified specialist company.
Procedure
1. Screw the connecting cable for the SCALANCE W-700 to the antenna. The
tightening torque at the N connector is 1 Nm. If there is greater mechanical load
(for example vibration) a maximum 3 Nm is permitted.
2. Provide strain relief for the cables.