Installing
4.2 Install
7. With small pipe diameters, mount the sensors upstream at an angle
bend
Figure 4-2
8. Use required torque values between device extension and protective tube as in Table 8-
14 Torque values between device extension and protective tube (Page 56).
– If customer adjustments are necessary (M24 connections only), use required torque
– For SITRANS TS500 barstock version (only European portfolio 7MC752..) without
See also
Construction (Page 56)
28
.
At a right angle to the flow
In a bend upstream
In an angle upstream
Possible mounting positions of the sensor
values between device head and extension as in Table 8-15 Torque values between
device head and extension (Page 56).
flange (type 4), use required torque values to complete the mounting of the device
extension to the protective tube as in Table 8-14 Torque values between device
extension and protective tube (Page 56).