INSTALLATION AND MAINTENANCE INSTRUCTIONS
FTX-P1 Filtrex
®
Photoelectronic Smoke Detector
Specifications
Operating Voltage Range:
Detector Current:
Auxiliary Power Supply Voltage:
Auxilary Power Supply Current –
Peak:
Average:
Operating Humidity Range:
Operating Temperature Range:
Height:
Diameter:
Weight:
Compatibility:
Mounting Base:
Before Installing
This detector must be installed in compliance with the
control panel system installation manual. The installation
must meet the requirements of the Authority Having Juris-
diction (AHJ). Detectors offer maximum performance
when installed in compliance with the National Fire Pro-
tection Association (NFPA); see NFPA 72.
General Description
Filtrex® uses a small air intake fan and a high density re-
placeable filter. Air and smoke are drawn into a photoelec-
tric sensing chamber while airborne particulate and water
mist are removed. The addressable-analog detector trans-
mits an analog representation of smoke density over a com-
munication line to a control panel. Rotary-decade switches
are provided for setting the sensor's address. Two LEDs on
the sensor are controlled by the panel to indicate sensor
status.
Filtrex smoke detector is intended for use in normal en-
vironmental conditions, where dust and other airborne
particulate are present at elevated levels. These elevated
levels tend to cause false alarms and high maintenance
in standard detectors. Filtrex provides a protective enclo-
sure for a photoelectric smoke detector chamber and al-
lows smoke detection in areas that tended to use
exclusively heat detection.
Filtrex requires compatible addressable communications
to function properly. Connect this detector to listed-com-
patible control panels only.
D200-72-00
Intelligent
15 to 32 VDC
230 A @ 24 VDC (without communication)
285 A @ 24 VDC (one communication every 5 sec. with LED enabled)
15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.
123 mA max.
27 mA max.
10% to 93% Relative Humidity, noncondensing
0 to 50 C (32 to 122 F)
2.8 inches (43 mm)
6.1 inches (155 mm) installed in B501B-FTX
4.0 inches (102 mm) installed in B524FTXE
7.3 oz. (207 g)
Backwards compatible with 200 and 500 series products' protocol
Requires B501B-FTX (U.S.), B524FTXE (Europe)
Spacing
System Sensor recommends spacing detectors in compli-
ance with NFPA 72. In low air flow applications with
smooth ceilings, space detectors 30 feet apart. For specific
information regarding sensor spacing, placement, and spe-
cial applications, refer to NFPA 72 or the System Sensor
Guide For Proper Use of System Smoke Detectors, available
from System Sensor (P/N I56-407-XX).
Filtrex is not designed to operate in explosive environments.
1
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
WARNING
I56-1184-04R

Advertisement

Table of Contents
loading

  Related Manuals for System Sensor FTX-P1

  Summary of Contents for System Sensor FTX-P1

  • Page 1 30 feet apart. For specific information regarding sensor spacing, placement, and spe- cial applications, refer to NFPA 72 or the System Sensor Guide For Proper Use of System Smoke Detectors, available from System Sensor (P/N I56-407-XX).
  • Page 2 Figure 1. Wiring diagram: – AUX. POWER SUPPLY – Wiring Instructions All wiring must be installed in compliance with the Na- tional Electrical Code, applicable local codes, and any spe- cial requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting.
  • Page 3 Figure 2. Rotary decade address switches: Figure 3. Test magnet position: Figure 4. Replacing the filter cover: Cover is keyed to fit into 4 matching size slots. Alignment marks are provided on the cap and top of the permanent filter. D200-72-00 the detector still fails any test, have its filter replaced (see in- structions below) and retested.
  • Page 4 B524FTXE Mounting Base. Please refer to insert for the Limitations of Fire Alarm Systems System Sensor warrants its enclosed smoke detector to be free from de- fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector.