System Sensor TEMPORAL TONE SOUNDER BASE B501BHT Installation And Maintenance Instructions
System Sensor TEMPORAL TONE SOUNDER BASE B501BHT Installation And Maintenance Instructions

System Sensor TEMPORAL TONE SOUNDER BASE B501BHT Installation And Maintenance Instructions

Temporal tone sounder base

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
B501BHT
Temporal Tone Sounder Base

Specifications

Base Diameter:
Base Height (less sensor):
Weight:
Operating Temperature Range:
Operating Humidity Range:

Electrical Ratings

External Supply Voltage:
Standby Current:
Alarm Current:
Maximum Ripple Voltage:
Start-up Capacitance:
Communication/Initiating Loop Supply
Current Draw from Remote Output
of Sensor to turn on Horn:
Sound Output:
Before Installing
Please read the System Smoke Detector Application Guide,
which provides detailed information on sensor spacing. place-
ment, zoning, wiring, and special applications. Copies of this
manual are available from System Sensor. NFPA 72 and NEMA
guidelines should be observed.
NOTICE: This manual should be left with the owner/user of
this equipment.
IMPORTANT: The detector used with this base must be tested
and maintained regularly following NFPA 72 requirements.
The detector should be cleaned at least once a year.

General Description

The B501BHT sounder base is used with System Sensor 200
and 500 Series sensor heads. Refer to the appropriate manual
for more information on sensors.
The B501BHT incorporates the distinctive three-pulse tempo-
ral pattern fire alarm evacuation signal now required by NFPA
72 for commercial and residential applications.
The sounder base is intended for use with intelligent systems.
Refer to the panel manual for the maximum allowable num-
ber of units per loop. The sounder base requires an external
24VDC supply with reverse polarity capability or a relay mod-
ule configured to reverse the power as in Figure 5. The con-
nections for the external supply (terminals 1 and 2) and the
communication loop (terminals 3 and 4) are isolated to pre-
vent electrical interaction between them.
When the sensor's visible LEDs are latched on for approxi-
mately 10 seconds, the associated horn sounds. A loop of
horns can be made to sound by reversing the polarity of the
external supply when configured as in Figure 4 and 5. When
configured as in Figure 5, a loop of horns can also be made to
sound by turning on the Intelligent Relay Module.
D550-06-00
6.0 inches (15.2 cm)
2.3 inches (5.9 cm)
0.4 lb. (181 gm)
32° to 120°F (0° to 49°C)
10% to 93% Relative Humidity
17 to 32 VDC
1.0 mA maximum
15 mA maximum
10% of supply voltage
200 µF
700 µA maximum
Greater than 90 dBA measured in anechoic room at 10 feet, 24 volts. 85 dBA minimum
measured in UL reverberant room.
NOTE: When not used as a supplementary evacuation system
the external 24 VDC supply shall be treated as a component of
the main power supply system and shall fall under the require-
ments of the main power supply system per NFPA 72.

B501BHT Terminals

No.
1
2
3
4
5
Terminals 3 and 4 are used for the communication circuit.

Mounting

Mount the B501BHT directly to an electrical box, using the
mounting kit, supplied (see Figure 2).
The sounder base is 1.1-inches deep. Electrical boxes must
be 4-inches square by at least 1
recommended.
NOTE: A maximum space of
the electrical box to the inside edge of the drywall or ceiling
tile is allowable.

Wiring Guidelines

All wiring must be installed in compliance with the National
Electrical Code and the local codes having jurisdiction and
must not be of such length or wire size which would cause
the base to operate outside of its published specifications. The
conductors used to connect smoke sensors to control panels
and accessory devices should be color coded to reduce the
likelihood of wiring errors. Improper connections can prevent
a system from responding properly in the event of a fire.
1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Function
External Supply Positive (+)
External Supply Negative (–)
Negative (–) Comm. Line In and Out
Positive (+) Comm. Line In and Out
Sounder Base Interconnect
1
2
1
inch from the outside edge of
8
www.systemsensor.com
inches deep - 2
1
inches is
8
I56-1367-004R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TEMPORAL TONE SOUNDER BASE B501BHT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for System Sensor TEMPORAL TONE SOUNDER BASE B501BHT

  • Page 1: Specifications

    Copies of this manual are available from System Sensor. NFPA 72 and NEMA guidelines should be observed. NOTICE: This manual should be left with the owner/user of this equipment.
  • Page 2 For signal wiring (the wiring between interconnected sensors or modules), it is recommended that the wire be no smaller than 18 gauge (1.0 square mm). Wire sizes up to 12 gauge (2.5 square mm) may be used with the base. For best system per- formance, the power (+ and –) wires and the communication circuit wires should be twisted pair or shielded cable installed in separate grounded conduit to protect the communication...
  • Page 3 Figure 4. Wiring diagram: Detector Activates Sounder Base(s) - (Complies with UL268) UL has approved grouping for up to six B501BHT base with horn units. When wired as a group, any detector in the group that has its LED’s latched on by the panel will cause other B501BHT units in the group to sound.
  • Page 4 Please refer to insert for the Limitations of Fire Alarm Systems System Sensor warrants its enclosed smoke detector base to be free from defects in mate- rials and workmanship under normal use and service for a period of three years from date of manufacture.