1. Safety Guidelines

1. Follow the installation instructions.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the appli-
cations detailed in these installation instructions. Any
other use will not be considered to comply with require-
ments and would invalidate the warranty.
4. Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried out by
authorized persons.
5. Immediately rectify any malfunctions which may influence
safety.
2. Description of function
The temperature relief valve is controlled by the supply
temperature of the heat exchanger. It consists of a spring-
loaded valve and a temperature sensor, which is acting on a
bellows system. When the supply temperature in the boiler
reaches the specified opening temperature (see Options), the
force in the bellows system exceeds the spring force of the
valve, and the valve opens.
In the case of installation upstream of the boiler, in the
cold-water supply of the boiler's integrated heat
exchanger:
The temperature relief valve closes the supply to the heat
exchanger. The heat exchanger itself remains dry in normal
operation. When the temperature relief valve is opened, the
heat exchanger fills up and dissipates excess heat from the
heating water to the drain.
In the case of installation downstream of the boiler, at the
hot-water outlet:
The temperature relief valve closes the outlet. When the
temperature relief valve opens, the heated city water is
drained from the heater and replaced with cold water from the
supply. This water can now absorb the excess heat from the
water heater to prevent overheating.
1
Safety heat exchanger
2
Cold-water supply
3
Outlet
4
min. DN20 (3/4")
3. Application
Solid/dual-fuel boilers with integrated water heater or cooling
coil in closed heating systems according to EN12828.
Honeywell GmbH
EN
4. Technical data
Medium
Heating
system capacity
Opening temperature
Ambient temperature
Capacity
Connection size
Operating pressure
Principal of operation
5. Scope of delivery
The temperature relief valve comprises:
• Housing with internal thread
• Bonnet
• Valve piston with form seal
• Spring
• Remote double temperature sensor with capillary tube
• Immersion sleeve G
6. Options
TS131-3/4A =
Opening temperature 95 °C
Capillary tube with protection sheath
1300 mm, with approved construction
TS131-3/4B =
Opening temperature 95 °C
Capillary tube with protection sheath
4000 mm
TS131-3/4ZAx = Opening temperature x = 50 °C / 100 °C or
110 °C
Capillary tube with protection sheath
1300 mm, with approved construction
7. Assembly
7.1. Installation instructions
• The valve and the sensor must be installed carefully to
avoid damaging the capillary tube
• The opening on the blow-out line must be clear and easy
to monitor
• Ensure no persons are in danger when blowing off the
fitting
• A sufficiently dimensioned discharge line must be provided
p = 1 bar
k
value
vs
3 m
/h
with 2 intact sensor systems
3
(with a media temperature of 110 °C)
2.1 m
/h
with one sensor system
3
(with a media temperature of 110 °C)
Caution! Installation of the thermal discharge safety
valve does not replace the diaphragm relief valve in the
cold water supply line to the water heater
4
Water
max. 100 kW
see Options
max. 70 °C
2800 kg/h water with a pressure loss
of p = 1 bar (1 sensor) at a media
temperature of 110 °C
Rp
/
" (DIN EN 10226)
3
4
max. 10 bar
2 KP
/
" (ISO 228)
1
2
MU1H-1543GE23 R0515