Figure 42 Smoke match tube
position
13.2 Check For Spillage
A spillage check must be made before leaving the installed appliance with the
customer. Make this check with the appliance fully installed with the ceramic fuel
effects and front surround in position.
13.2.1 Close all doors and windows in the room containing the appliance.
13.2.2 Turn on the fan. Light the appliance. Turn the control to "HIGH".
13.2.3 Leave the appliance on for five minutes
13.2.4 Place the smoke match tube into the convection box at the right
hand side and immediately below the black top cross member. Angle it at
approximately 45° to the horizontal(fig. 42).
Insert the tube so that the neck of its flared end touches the inside surface
of the edge of the cross member (figure 42).
Keeping the neck of flared end in contact with the edge of the cross
member, slide the tube to the left until you feel it enter the notch in the
edge of the cross member. Make sure that the tube is pointed upwards at
45º to the horizontal.
The installation is satisfactory if the smoke is drawn into the appliance. If
the smoke is not drawn into the appliance the powered fan is not operating
correctly. Do not allow the appliance to be used until the fault is corrected.
13.2.5 If the above test is satisfactory, open all internal connecting doors,
hatches, etc. in the room. Switch on any extractor fan or other air circulating
system installed in the same room as the appliance or in a connecting room.
Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above.
If the smoke is drawn into the appliance, continue with the installation. If the
test is not satisfactory, Disconnect the appliance and advise the customer of the
cause of failure.
13.2.6If any other non-sealed gas appliances are installed in the room or
connecting rooms, check that to ensure that there is no spillage from these
appliances when Model BR517 is operating with its fan on. Check these other
appliances by the procedure supplied by the manufacturer.
13.3 Flame Supervision & Spillage Monitoring System
This pilot unit incorporates a system which will automatically shut off the gas
supply if the pilot flame goes out or if there is insufficient oxygen due to spillage
or lack of ventilation.
Check that the system operates properly as follows;
13.3.1 Turn on the fan. Light the appliance and turn the control knob to
"HIGH". Leave for one minute.
13.3.2 Turn back to "OFF" to extinguish the pilot. Note the time when the pilot
goes out. Listen for a snap sound at the gas tap. Note the time when the sound is
heard. This sound is caused by an electromagnetic valve shutting off the gas
supply through the tap. The valve is located in the body of the tap. The valve
should operate within 60 seconds of the pilot going out. If the valve does not
operate within this time limit do not allow the appliance to be used until the
fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system, or any of its parts, must only be exchanged using Valor
authorised parts.