Example
You have set a dark test time of 100 ms, a light test time of 2 ms and the PM-switching
mode. You have set the load current to 20 mA and the capacity to 100 µF. The operating
point is thus outside the range defined by the two trends (gray background).
Solution: Select an actuator with higher current consumption. In this example, 40 mA.
Alternatively, you can configure the parameter "Max. readback time dark test" with 200 ms.
B.2
Switching of inductive loads
Switching of inductive loads
Use the switchgear for control and auxiliary circuits according to the utilization category
DC-13 in accordance with IEC 60947-5-1:2014.
Digital output module F-DQ 8x24VDC/2A PPM (6ES7526-2BF00-0AB0)
Manual, 01/2016, A5E03858037-AA
Switching of loads
B.2 Switching of inductive loads
57