Diagnostic alarm

Supply voltage missing

Safety event
Mismatch of safety destina-
tion address (F_Dest_Add)
Safety destination address
not valid (F_Dest_Add)
Safety source address not
valid (F_Source_Add)
Safety watchdog time value
is 0 ms (F_WD_Time)
Parameter F_SIL exceeds
SIL from specific device
application
Parameter F_CRC_Length
does not match the generat-
ed values
Version of F-parameter set
incorrectly
CRC1 fault
Save iParameter watchdog
time exceeded
Restore iParameter watch-
dog time exceeded
Inconsistent iParameters
(iParCRC error)
F_Block_ID not supported
Digital output module F-DQ 8x24VDC/2A PPM (6ES7526-2BF00-0AB0)
Manual, 01/2016, A5E03858037-AA
Fault
Meaning
code
17
Missing or insufficient supply voltage L+
D
25
For safety purposes, channel was
D
switched off due to an error on another
channel.
Possible causes:
A short-circuit exists.
The capacitive load is too high (PP-
switching operation).
64
The firmware of the F-module has de-
D
tected a different F-destination address.
65
The firmware of the F-module has de-
D
tected an illegal different F-destination
address.
66
The firmware of the F-module has de-
D
tected a different F-source address.
67
The firmware of the F-module has de-
D
tected an invalid watchdog time.
68
The firmware of the F-module has de-
D
tected a discrepancy between the SIL
setting of the communication and the
application.
69
The firmware of the F-module has de-
D
tected a discrepancy in the CRC length.
70
The firmware of the F-module has de-
D
tected an incorrect F_Par_Version or an
invalid F_Block_ID.
71
The firmware of the F-module has de-
D
tected inconsistent F-parameters.
73
iPar server does not respond to "save
D
IPar" within 4.4 minutes.
74
iPar server does not respond to "restore
D
IPar" within 4.4 minutes.
75
The firmware of the F-module has de-
D
tected inconsistent iParameters.
76
The firmware of the F-module has de-
D
tected an incorrect block ID.
Interrupts/diagnostic messages
6.3 Diagnostic alarms
Remedy
Check supply voltage L+ at the
front connector
Check the front connector
Correct the process wiring.
Increase the test times (dark, light,
switch-on tests).
Check the parameter assignment
of the PROFIsafe driver and the
PROFIsafe address assigned to
the F-module.
Assign the PROFIsafe address to
the F-module (again).
Check the configuration/parameter
assignment of the iPar server.
Check the configuration/parameter
assignment of the iPar server.
Check the parameter assignment.
Check the parameter assignment of
the PROFIsafe driver.