Cables - Fasel Elektronik FCU2000 Series Installation Instructions Manual

Steam bath control
Hide thumbs Also See for FCU2000 Series:
Table of Contents

Advertisement

2.4

Cables

Use of
inappropriate
cables –
Electric
potential
Designation
Power supply cables
230 / 400V cables for
supply to oven, blower, light
etc.
Signal cables for sensors
Connecting cable
Control device to
operating element or
interior display
Specification of the patch
cable
Conduit for patch cable
Table 4: Technical data– cables
Installation instructions Steam bath control Series FCU2000/FCU3000/FCU4000/FCU5000 M_FCUxxxx-Steam_EN / Version V2.04 11
DANGER!
Danger to life due to electric potential
Use of inappropriate cables can lead to short circuits and subsequent
fires.
Damage to the insulation can be dangerous to life.
Therefore:
– All the cables, which lead to the steam bath, must be designed for at
least 150° C.
– Use cables as per specifications in table 2 and electrical circuit
diagram (page 29, Figure 11). The specified cross sections are
designed for copper cables. In case of aluminium cables the cross
sections should be appropriately increased.
– The cross sections can increase due to the length of the cables, the
type of cable laying or special regulations.
Type
FCUxxxx-Steam
Type /
H07RN-FG2,5
Cross
(heavy rubber hose 5 x 2,5 mm
section /
Power supply cables must be polychloroprene-coated and
Number of
should not be lighter than heavy polychloroprene-coated
leads
flexible cables.
Type
Heat resistant, at least 150 ° C
Cross
→ See electrical circuit diagram, page 29, Figure 6.
section
Number of
→ See electrical circuit diagram, page 29, Figure 11.
leads
Type
In case of longer distances: LiYCY
(flexible, shielded cable)
Within the cabin: heat resistant,
minimum 150 ° C
Cross
→ See also installation plans page 21 ff., section 6.3.
section
Number of
→ S See also installation plans page 21 ff., section 6.3.
leads
The patch cable can be delivered with a standard length of 5 or 10m. If
another length is desired then the cable must be configured by the
electrician. Another option would be to bridge a stretch by installing two
network sockets (CAT 5).
Minimum CAT 5, minimum AWG26
Plugs should have no rubber covering over the locking mechanism
Pin 1 to Pin 1 cable configuration (straight through)
Min. M32 (inner diameter min. 24mm), smallest bending radius 30 cm
Technical data