Swegon COOL DX 008 Installation And Maintenance Instructions Manual page 8

Table of Contents

Advertisement

GB.COOLDX.SI.G.190603
3.3.1
Height adjustment to the height of the SIL-
VER C/water trap
COOL DX, size 008
In combination with the SILVER C RX 08
The SILVER C air handling unit can be mounted on base
beams, a stand or some other form of foundation. Base
beams and stands are available as accessories.
Appropriate base beams and stands are also available as
accessories for the COOL DX. The base beams/stands are
matched to one another in terms of height. The stands
also provide space for accommodating a possible water
trap in the lower level (right-hand unit version).
In combination with the SILVER C PX 008
The air handling unit is supplied with base beams. A set of
legs (accesssory) can be mounted in the base beams.
Appropriate base beams and set of legs are also available
as accessories for the COOL DX. The base beams/sets of
legs are matched to one another in terms of height. The
sets of legs also provide space for accommodating a pos-
sible water trap in the lower level (right-hand unit version).
COOL DX, sizes 012-080
The SILVER C air handling unit and the COOL DX cooling
unit are supplied with a 100 mm high base beam.
Applicable to a cooling coil in the lower level:
If a water trap (accessory) is fitted, the SILVER C air han-
dling unit and the cooling unit must be raised at least 50
mm to provide space for the water trap. Adjustable sup-
port feet (accessories) can be appropriately fitted to the
base beams for this purpose.
8
www.swegon.com
We reserve the right to alter specifications.