Ratings And Dimensions; Fe Ul Ratings And Dimensions In Common - Bosch REXROTH EFC 3600 Instruction Manual

Frequency converters
Hide thumbs Also See for REXROTH EFC 3600:
Table of Contents

Advertisement

DOK-RCON01-REX*F*UL***-IN01-EN-P
Rexroth Frequency Converters
3

Ratings and Dimensions

3.1

Fe UL Ratings and Dimensions in Common

Description
Listing according to UL standard (UL)
UL files (UL)
Enclosure
Pollution degree (UL)
Ambient temperature with nominal data (UL)
Ambient temperature with reduced nominal da‐
ta (UL)
Minimum distance on the top of the device
Minimum distance on the bottom of the de‐
vice
2)
Horizontal spacing on the device
Short circuit current rating (UL)
Rated input voltage, power (UL)
Tolerance rated input voltage (UL)
Input frequency (UL)
Tolerance input frequency (UL)
Field wiring material (material; conductor tem‐
perature; class)
Output voltage (UL)
Output frequency range (UL)
Fig.3-1: Fe - UL Ratings and Dimensions in Common
Symbol
1)
3)
4)
5)
Bosch Rexroth AG
Ratings and Dimensions
Unit
Data
NMMS.E328841
T
°C
amax
T
°C
amax_red
d
mm
top
d
mm
bot
d
mm
hor
SCCR
A rms
U
V
LN_nenn
%
f
Hz
LN
Hz
U
V
out
f
Hz
out
UL 508 C
Open type
2
40
50
150
150
50
5000
(0K75 to 90K0)
42000
(110K to 160K)
3 x AC
380...480
-15...+10
50...60
± 5
Copper;
60/75°C
(0K75 to 22K0)
Copper; 75 °C
(30K0 to 160K)
Corresponding
to input voltage
0...650
29/65

Advertisement