Dual Fuel Burner; Adjusting Gas Side - Weishaupt W-FM 25 Manual

Hide thumbs Also See for W-FM 25:
Table of Contents

Advertisement

83294002 • 2/2014-11 • La
Installation and operating instruction
Replacing combustion manager W-FM 20 ... 24 with W-FM 25
6 Commissioning

6.4 Dual fuel burner

6.4.1 Adjusting gas side

1. Preset combustion manager
Set fuel selection switch to GAS.
Unplug bridging plug No. 7 on combustion manager.
Switch on voltage supply.
The unprogrammed condition of the combustion manager is indicated by a flashing
display.
The burner goes to lockout.
Press [ENTER] key.
Burner has been reset.
Combustion manager drives to Standby.
Press [G] and [L/A] simultaneously.
Combustion manager changes to access level.
Press [+].
Setting level (parameter E0 ) is displayed.
Set value 1 (dual fuel burners) using [ENTER] and [+] key.
Press [+].
E1 is displayed.
Adopt value 0 (intermittent operation) using [+] key.
E2 is displayed.
47-70