ENDA ET2011
ON/OFF and PID TEMPERA
Thank you for choosing ENDA ET2011 temperature controller.
* 77 x 35mm sized.
* Selectable dual-set value.
* Selectable thermocouple types or Pt100 input.(Selection must be
specified in order).
* Automatic calculation of PID parameters.(SELF TUNE).
Enter PID parameters of the system if they are known at the beginning.
Otherwise, Self-Tune should be activated.
* Soft-Start feature.
* Input offset feature.
* C/A2 Relay output can be programmable as alarm or control output.
* Selectable SSR control output.
* Selectable heating/cooling control.
* In the case of sensor failure periodical running or relay state can be
selected.
* CE marked according to European Norms.

TECHNICAL SPECIFICATIONS

Input type
Pt 100 Resistance thermometer
Pt 100 Resistance thermometer
J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt10Rh-Pt) Thermocouple
R (Pt13Rh-Pt) Thermocouple

ENVIRONMENTAL CONDITIONS

Ambient/storage temperature
Max. Relative humidity
Rated pollution degree
Height
Do not use the device in locations subject to corrosive and flammable gases.

ELECTRICAL CHARACTERISTICS

Supply
Power consumption
Wiring
Line resistance
Data retention
EMC
Safety requirements

OUTPUTS

C/A2 output
SSR output
Life expectancy for relay

CONTROL

Control type
Control algorithm
A/D converter
Sampling time
Proportional band
Control period
Hysteresis
Output power

HOUSING

Housing type
Weight
Enclosure material
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Temperature range
°C
EN 60751
-99.9...300.0 °C
EN 60751
-200...600 °C
0... 600
°C
EN 60584
EN 60584
0...1300
°C
EN 60584
0... 400
°C
EN 60584
0...1700
°C
EN 60584
0...1700
°C
0 ... +50
°C -25... +70°C (with no icing)
/
80
%
up to 31
°C
decreasing linearly 50
According to EN 60529
Max. 2000m
230V AC +%10 -%20, 50/60Hz or 24V AC
Max. 5VA
Power connector: 2.5mm²' screw-terminal, Signal connector: 1,5mm² screw-terminal conenction.
Max. 100ohm
EEPROM (minimum 10 years)
EN 61326-1: 2006
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
Röle : 250V AC, 8A (for resistive load), Selectable as NO+NC Control or Alarm2 output.
Röle : 250V AC, 16A (for resistive load), Selectable as NO Control or Alarm2 output.
Max 20mA 12Volt (as control output)
Withot load 30.000.000 mechanical operation; 250V AC, on the 8A resistive load 100.000
Single set-point and alarm control
12 bit
100ms
Adjustable between 0
%
and 100 . If Pb=0 , On-Off control is selected.
Adjustable between 1
and 250 seconds
Adjustable between
1 and 50
°C/F
The ratio of power at a set point can be adjusted between 0
Suitable for flush-panel mounting according to DIN 43 700.
W77xH35xD71mm
Approx. 200g (after packing)
Self extinguishing plastics.
TURE CONTROLLER
°F
C/A2
ENDA
°F
-99.9...543.0 °F
-328...1112 °F
+32... +1112
°F
+32... +2372
°F
+32... +752
°F
+32... +3092
°F
+32... +3092
°F
%
at 40.
Front panel :
IP65
Rear panel :
IP20
%10, 50/60Hz
electrical switching
%
%
%
and 100
1/4
SSR
F
°C
SET
SET
ET2011
Accuracy
0,5% (of full scale)
1 digit
0,5% (of full scale)
1 digit
0,5% (of full scale)
1 digit
0,5% (of full scale)
1 digit
0,5% (of full scale)
1 digit
0,5% (of full scale)
1 digit
0,5% (of full scale)
1 digit
%
ET2011-E-04-R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ET2011 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ENDA ET2011

  • Page 1: Technical Specifications

    Also we don't accept any compensations for personal injury, material damage or capital disadvantages. ENDA ET2011 ON/OFF and PID TEMPERA TURE CONTROLLER Thank you for choosing ENDA ET2011 temperature controller. * 77 x 35mm sized. °F C/A2 * Selectable dual-set value.
  • Page 2 C. Ct m. s Et. While the parameter names appear,if C. P . S t keys are pressed together, returns to the program C. E P. S mode. S. s . t . S C. t yp HEat ET2011-E-04-R...
  • Page 3 (F. k . E . C . parameter processing) ( 2) Value decrement and parameter selection key. (Programming mode) ENDA ET2011 ( 4 ) Control ve Alarm set selection key (Running mode) Parameter set key (Programming mode) ( 1 ) PV and SV display...
  • Page 4 CONNECTION DIAGRAM ENDA ET2011 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy.

Table of Contents