13.4 Status word

Status Word
Bit
Meaning
0
always 0 (LSB)
1
always 0
2
always 1
3
always 0
4
always 0
5
always 0
6
always 0
7
always 0 (MSB)
8
0/1 = no load/ load
9
0/1 = no magnetic influence / magnetic influence
10
0/1 = terminal cover closed/terminal cover opened
11
0/1 = +A/-A current energy direction
12
0/1 = +A/-A current energy direction L1
13
0/1 = +A/-A current energy direction L2
14
0/1 = +A/-A current energy direction L3
15
0/1 = +A/-A phase sequence
16
0/1 = off/on reverse locking
17
0/1 = no/fatal error (billing relevant error)
18
0/1 = off/ on voltage L1
19
0/1 = off/ on voltage L2
20
0/1 = off/ on voltage L3
21-31
reserved

Table 13 Status word

Copyright  DZG Metering GmbH, Heidelberger Str. 32, D-16515 Oranienburg
22.02.2019
Kopien nur mit Erlaubnis der DZG
Page 37 / 38