Download Print this page

Specifications; Ordering Information - Honeywell M7164 Manual

Modutrol iv motors
Hide thumbs

Advertisement

M7161, M7164, M7184
SPECIFICATIONS • ORDERING INFORMATION
MODELS:
M71 6 1 A,B,G
M71 6 4 A,B,G
M71 8 4 A
Control Type
71 is dc voltage input
0.8-3.3, 4-7, 6-9 or
10.5-13.5 Vdc
Power Rating
6 is low power—
35 lb-in. torque
8 is high power—
150 lb-in. torque
Output Drive
4 is dual-ended shaft, nonspring return.
1 is single-ended shaft, nonspring return.
MOTOR ROTATION:
Normally closed M7161A,B and M7164A,B; M7184A
drives to fully counterclockwise
from the power end) to the fully closed position when
powered input signal is at a minimum.
Electrically normally open M7161G and M7164G drive
clockwise
the fully open position when the powered input signal
is at a minimum.
STROKE: Fixed 90° or 160° stroke models available.
TIMING: Nominal 30 seconds for 90° stroke and 60 seconds
for 160° stroke.
DEAD WEIGHT LOAD ON SHAFT:
M7161
100 lb (45.4 kg)
M7164
100 lb (45.4 kg)
M7184
200 lb (90.8 kg)
300 lb (136.2 kg) maximum combined (power and auxil-
iary end) dead weight load.
When purchasing replacement and modernization products from your wholesaler or your distributor, refer to the price sheets for
complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Satisfaction
Honeywell Inc.,
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales
and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan,
Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Suffix Letter
A: is fixed stroke
(90° or 160°), electrically
normally closed,
no auxiliary switches.
B: is fixed stroke
(90° or 160°), electrically
normally closed,
1 auxiliary switch.
G: is fixed stroke
(90° or 160°), electrically
normally open,
no auxiliary switches.
(as viewed
(as viewed from the power end) to
Power End
Auxiliary End
N/A
100 lb (45.4 kg)
200 lb (90.8 kg)
MAXIMUM DAMPER RATING:
M7161A,B,G and M7164A,B,G: B dimension = 48 in.
M7184A: B dimension = 202 in.
AMBIENT TEMPERATURE RATINGS:
Maximum: 150° F [66° C] at 25% duty cycle.
Minimum: -40° F [-40° C].
SHAFT: 3/8 in. [9.5 mm] square.
M7161 Models: Single-ended shaft.
M7164 and M7184 Models: Dual-ended shaft.
DIMENSIONS: See Fig. 1.
UNDERWRITERS LABORATORIES INC. LISTED:
File No. E4436, Guide No. XAPX.
CANADIAN STANDARDS ASSOCIATION CERTIFIED:
General Listing File No. LR1620, Guide 400-E.
ELECTRICAL RATINGS:
Voltage
Vac @
50/60 Hz
M7161
24
M7164
120
M7184
24
AUXILIARY SWITCH RATINGS (Amperes):
One Contact
a
Rating
Full Load
Locked Rotor
a
40 VA pilot duty, 120/240 Vac on opposite contact.
ACCESSORIES:
ES650117 Explosion-proof Housing: Encloses motor for
use in explosive atmospheres. Not for use with Q601,
Q618, and Q455 Linkages. Order separately from Nelson
Electric Co. Requires Honeywell 7616DM Coupling.
Q607 External Auxiliary Switch: Controls auxiliary equip-
ment as a function of motor position.

Ordering Information

2

Specifications

Current
Power Con-
Draw (A)
sumption (W)
0.62
14
0.20
19
0.80
18
120V
240V
7.2
3.6
43.2
21.6

Advertisement

loading

This manual is also suitable for:

M7184M7161