Electrical Power Connection
When ferrules are used, the maximum connectable line cross
section may be reduced.
The control connections are situated under the terminal cover of the frequen‐
cy converter.
Terminals:
Plug-in clamp connectors are unlocked with a small screwdriver.
Maximum connection cross section:
1.0 mm
2
(26-14 AWG)
Relay = 1.5 mm
2
(26-16 AWG)
Control lines:
Run and shield separately from mains/motor lines
Control voltages:
5V ± 20%, max. 250 mA
(short-circuit proof) 10V, max. 5 mA, reference voltage for an ext. potentiom‐
eter
15V ± 20%, max. 150 mA, for supplying the dig. inputs
Analog output 0... 10V, max. 20 mA, for an ext. display unit