Multi application quick health check

Using diagnostic Led, present on to the Multi main board, it is possible
to perform a first quick check of the application without the use of SW
tools.
Check the chapter "MULTI DEVICE ANATOMY" on page 58 for LED
and reset button positions.
The below table shows the checks that is possible to perform, the Led
to be checked and possible approaches to overcame the issues.
Function
Ethernet
Communication
Application
running
EBI
communication
Data Base
status
66
Led and
Possible
status
failure(s)
RJ45.1
No Ethernet
communication
OFF
CR78
Application not
running
OFF
CR96
No communication
with EBI
ON
CR25
Database not
present
ON
Table 10 – Multi application quick health checks
Approach
Check the Ethernet
wiring.
Check the status of the
network.
Reset the device using
reset button.
Check if the
supervision centre is up
and running
Check if the Multi
device is properly
configured into EBI.
Check the Ethernet
communication.
Without supervision centre
communication there will
not be any DB download,
so:
Check if the
supervision centre is
up and running.
Check if the Multi
device is properly
configured into EBI.
Check the Ethernet
communication.