11. External input and output (for AOTG34KMTA)
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
Connector
CN10
Low noise mode
CN11
Peak cut mode
CN12
CN13
11-1. External input
With using external input function, on/off status of "Low noise mode" and "Peak cut mode" can be
specified by the external signal.
Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in
normal operating condition:
• The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
NOTE: Product performance may drop depending on some conditions such as the outdoor
temperature.
Circuit diagram example
Outdoor unit
control PCB
Connector
1
2
Input signal
Low noise mode
Optional part
Part name
External connect kit
Input
—
—
Compressor status
• Contact capacity: DC 24 V or more, 10 mA or more.
Connected unit
• *: Make the distance from the PCB to the connected
Example: Switch
• Construct a circuit as shown in this figure with using
• Input signal: On in "Low noise mode"
*10 m
• Input signal: Off in normal operation
• To set the level of "Low noise mode", refer to "Low
Signal
Locally purchased
On
Off
On
Off
Model name
UTY-XWZXZ3
- 64 -
Output
—
—
Error status
unit within 10 m.
optional parts mentioned below.
noise mode" on page 70.
Remarks
See external input/output
settings for details.
Exterior