OpenAir Non-Spring Return Rotary Electric Damper Actuator
24 Vac – Modulating Control
Wiring
•
All wiring must conform to NEC and local codes and regulations.
•
Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers.
•
The sum of the VA ratings of all actuators and all other components powered by one
transformer must not exceed the rating of the transformer.
•
It is recommended that one transformer power no more than ten actuators.
Wiring Designations
24 Vac power supply
0 to 10V modulating control
8
9
S1
A
M
S2 S3
1
2
Siemens Building Technologies, Inc.
WARNING:
All six outputs of the dual auxiliary switch (A and B) must only be connected to:
Class 2 voltage (UL/CSA).
Separated Extra-Low Voltage (SELV) or Protective Extra Low Voltage (PELV)
(according to HD384-4-41) for installations requiring
WARNINGS:
Installations requiring
•
All wiring for CE certified actuators must be "Separated Extra Low Voltage"
(SELV) or "Protective Extra Low Voltage" (PELV) rated per HD384-4-41.
•
Use safety-isolating transformers (Class III transformer) per EN61558.
They must be rated for 100% duty cycle.
•
Overcurrent protection for supply lines is maximum 10A.
Each wire has the standard symbol printed on it.
Standard
Symbol
1
2
8
S4
9
B
S1
S5 S6
S2
S3
S4
S5
S6
Conformance:
Table 4.
Function
Supply (SP)
Neutral (SN)
0 to 10V input signal
Output for 0 to 10 Vdc
position indication
Factory-installed Options
Switch A Common
Switch A - N.C.
Switch A - N.O.
Switch B - Common
Switch B - N.C.
Switch B - N.O.
Technical Instructions
Document Number: 155-187P25
November 30, 2005
conformance.
Terminal
Color
Designation
G
Red
G0
Black
Y
Gray
U
Pink
Q11
Black
Q12
Black
Q14
Black
Q21
Black
Q22
Black
Q24
Black
Page 11